Weil-McLain 550-110-260/0508 11d Troubleshooting — control module lights cont, Is FLAME light on?

Models: 550-110-260/0508

1 64
Download 64 pages 39.78 Kb
Page 53
Image 53
Is boiler System circulator operating?

GOLD CGs Gas-Fired Water Boiler — Boiler Manual Does voltmeter show 120 VAC across pins?

11d Troubleshooting — control module lights (cont.)

CHART 7 — Insufficient heat or no heat to system (POWER light on steady)

Electrical shock hazard — Wherever you see TURN OFF POWER , follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.

• Has it been at least 5 minutes since setting thermostat to call for heat? If not, wait 5 minutes. Is system heating?

• Is thermostat set to call for heat? Remove thermostat wires at boiler and check continuity across the two wires. If circuit isn't closed, check external thermostat (zone valve, relay, etc.) wiring. Correct problems and retry.

• Reconnect external thermostat wiring at boiler.

Is thermostat circuit closed (continuity across wires)?

No

 

Yes

Is boiler System circulator operating?

No

Yes

Remove CIRCULATOR harness plug from CIRCULATOR plug receptacle (Figure 25, Item 7, page 46). Check with voltmeter across pins of control module receptacle.

Does voltmeter show 120 VAC across pins?

No

Yes

Are all red lights off?

No

Yes

 

 

 

Wait 30 seconds. Are all red lights off?

No

Yes

 

 

 

Replace control module. Retest.

Boiler is in standby.

Set thermostat to call for heat and recheck

operation.

Verify Sequence of operation, Figure 18, page 31.

Replace control

 

Repair/replace

 

module.

 

 

circulator. Retest.

Retest.

 

Repair/replace

 

 

 

 

wiring. Retest.

 

 

 

 

 

 

 

 

 

• Wait 5 minutes.

 

Is FLAME light on?

Yes

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

If you have sufficient heat — boiler should be in normal operating sequence. (See normal sequence of operation, Figure 18, page 31.)

If you have less than sufficient heat —

 

Is LIMIT light on?

No

Yes

Is vent or combustion air piping free of blockage?

No

 

Yes

 

 

 

 

 

 

 

 

 

 

• Correct conditions and

 

Contact your Weil-McLain

recheck operation.

 

sales representative.

See Figure 18, page 31 for normal sequence of operation.

Wait for boiler water to cool to temperature 20 to 30 °F

lower than temperature set on limit switch.

Check limit switch contacts with continuity checker.

Are limit switch contacts

closed?

 

No

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

Replace control module.

Retest.

Check rollout switch continuity — is switch closed?

No

 

 

Yes

 

 

 

 

 

Are limit switch contacts closed?

 

No

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Boiler water temperature exceeded

 

 

 

 

setting on limit switch with thermostat

 

 

 

 

Replace

 

calling for heat. Boiler is OK. (See normal

 

sequence of operation, Figure 18, p. 31.)

 

limit switch.

 

 

 

• Also check setting on limit switch (should

Retest.

 

 

be above 140°F.).

 

 

 

 

• Replace rollout switch.

If rollout thermal fuse element has opened, determine cause and correct condition. Failure to do so will cause severe personal injury, death or substantial property damage.

Check any other limit controls wired into the limit circuit. If all are OK, then replace control module.

Retest.