TROUBLE SHOOTING CHART

GB

TROUBLE SHOOTING CHART

Thermostat is calling for heat

Burner is not running

Reset Control Box

Burner Starts

Burner Does Not Start

Test for 120Vac Supply at sub-base between L(P) & N or terminals #3 & 5

120 Vac

No Voltage

Check system fuse, ensure service switch is ON.

Verify all control limits are closed.

If using switching relay - verify 24Vac at T-T.

Turn off power supply - Remove control box and jumper terminals #5 & 6. Restore power.

Motor Runs

Motor Does Not Run

Verify electrical connections.

Check for seized pump, motor, or fan against housing.

Defective motor capacitor.

Thermal overload (Hot motor).

Verify reduced voltage (42-52 Vac) between terminals #3 & 7.

Ensure good contact between control box spades and sub-base terminals.

Defective control box / Replace.

Burner stays in Pre-purge

Faulty CAD cell or seeing light before trial for ignition.

Coil wire on terminals #1 & 2 or #1 & 8 reversed.

Open coil circuit, terminals #2 & 8.

Open coil circuit, terminal #1 (530 SE only).

Open coil circuit, terminal #1 (483 SE only) will cause burner to cycle normally, but burner will lockout.

Defective 42-52 Vac supply - Terminals #3 & 7.

Defective control box / Replace.

Burner Continues to Purge and Lightoff with

Immediate Flame Dropout. (530 SE Only)

Metal yoke for coil missing.

Coil wire #2 & 8 reversed.

Low resistance of coil holding circuit, terminals #1 & 2, (1350 ohms ± 10%).

Burner Locks Out After Trial For Ignition

Low resistance or no contact on starting circuit of coil, terminals #2 & 8. (1.3 ohm ± 10%)

No oil supply - tank empty, valve closed, dirty filter, damaged supply lines.

Defective or dirty oil valve stem, nozzle or pump strainer.

Broken pump drive key, defective pump, no oil pressure.

Ignition electrodes shorted, cracked porcelain.

Burner motor not up to speed.

Excessive draft over fire.

Defective control box / Replace.

Burner Fires-Cycles On & Off

In Quick Succession - (483SE Only)

Metal yoke for coil missing.

Low resistance or short in holding circuit of coil, terminal #1 & 2.

Coil wires on terminals #2 & 8 reversed.