8 | EG, PEG, EGH |
|
Check-out procedure
Check-out procedure
❏System properly filled with water?
❏Automatic air vent, if used,open one turn (water boilers only)?
❏Air purged from system (water boilers only)?
❏Steam boilers properly skimmed?
❏Air purged from gas piping?. Piping checked for leaks?
❏Are proper orifices installed? Check page 7 for proper size.
Proper orifices must be used. Failure to do so will cause severe personal injury, death or substantial property damage.
❏Follow operating instruction label on boiler for proper start- up.Also refer to“To Place in Operation,”page 17.
❏Proper burner flame? Refer to “Check Main Burner Flames” and“Check Pilot Burner Flame,”page 21.
❏Testlimitcontrol:Whileburnersareoperating,movelimitcontrol indicator below actual boiler water temperature or pressure. Burners should go off. Circulator should continue to operate (water boilers only). Raise indicator above boiler water temperature or pressure and burners should reignite.
❏Test any additional
❏EG only - button on spill switch pushed in?
❏To test ignition system
a.For boilers with electronic ignition systems: Connect manometer to outlet side of gas valve. Start boiler, allowing for normal
b.For standing pilot - Turn gas cock knob to PILOT position and extinguish pilot flame. Pilot gas flow should stop in less than 3 minutes. Put system back into operation (see page 17).
❏Limitcontrolsettodesigntemperatureorpressurerequirements of system? Maximum limit setting - 240°F (water boilers) - 15# (steam boilers).
❏ | For multiple zones, flow adjusted so it is about the same in |
| each zone (water boilers only)? |
❏Thermostat heat anticipator set properly? Refer to “Room Thermostat,”page 15 and correct wiring diagram.
❏Boiler cycled with the thermostat? Raise to highest setting. Boiler should go through normal
❏Measure gas input (natural gas only):
a.Operate boiler 10 minutes.
b.Turn off other appliances.
c.At the natural gas meter, measure time (in seconds) required to use one cubic foot of gas.
d.Calculate gas input:
3600 x 1000 | = Btuh |
|
number of seconds from step c
e.Btuh calculated should approximate input rating on rating label.
❏Check manifold gas pressure by connecting a manometer to the downstream test tapping on main gas valve.
MANIFOLD GAS PRESSURE NAT. = 3.5" W.C.
L.P. = 10.0" WC.
❏Several operating cycles observed for proper operation? If damper is provided, see Control Supplement for check- out procedure.
❏Room thermostat set to desired temperature?
❏Installation and Service Certificate on this page completed?
❏All instructions shipped with this boiler reviewed with owner or maintenance person, returned to envelope and given to owner or displayed near boiler?
Installation and Service Certificate
Boiler Model | Series |
| CP Number |
|
| Date Installed |
| |||
|
|
|
| ❏ |
|
|
|
|
|
|
BTU Input |
| Installation instructions have been followed. |
|
|
| |||||
|
|
|
| ❏ |
|
|
| |||
|
|
|
| ❏ | Above information is certified to be correct. |
|
|
| ||
|
|
|
| ❏ | Information received and left with owner/maintenance person. | |||||
Installer |
|
|
|
|
|
|
| |||
|
| (Company) | (Address) | (Phone) | (Installer's Signature) |