Weil-McLain EG Final adjustments, Water treatment, Filling water systems, Filling steam boilers

Models: EG

1 28
Download 28 pages 32.84 Kb
Page 16
Image 16
Final adjustments

7

EG, PEG, EGH GAS-FIRED BOILERS SERIES 4 — BOILER MANUAL

 

Final adjustments

Water treatment

Do not use petroleum-based cleaning or sealing compounds in boiler system. Severe boiler damage will occur.

Continual fresh make-up water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating cast iron, and causing section failure.

In hard water areas or low pH conditions (less than 7.0) consult local water treatment company.

Freeze protection (when used):

Use antifreeze especially made for hydronic systems.

Inhibited propylene glycol is recommended.

Do not use automotive, ethylene glycol or undiluted antifreeze. Severe personal injury, death or substantial property damage can result.

50% solution provides protection to about -30°F.

Local codes may require back-flow preventer or actual disconnect from city water supply.

Determine quantity according to system water content. Boiler water content is listed on page 27. Remember to add in expansion tank water content.

Follow antifreeze manufacturer’s instructions.

Filling water systems

1.Close manual air vents, drain cock, and automatic air vent, if used.

2.Fill to correct system pressure. Correct pressure will vary with each application. Residential systems are often designed for 12 pounds of cold fill pressure.

3.Open automatic air vent one turn, if used.

4.Open manual water feed valve.

a)Starting on lowest floor, open air vents one at a time until water squirts out. Close vent.

b)Repeat with remaining vents.

5.Close manual water feed valve when correct boiler pressure is reached.

6.If purge valve is used - located in the return piping above isolation valve:

a)Connect hose to purge valve.

b)Close isolation valve. Open purge valve.

c)Open hand water feed valve and allow system to purge all air. If system has more than one circuit, purge each circuit separately by opening each balancing valve one at a time.

d)Close purge valve and water feed valve cock.

e)Open isolation valve.

f)Fill system to correct pressure.

Filling steam boilers

1.Do not fill (except for leakage tests) until boiler is ready to be fired.

2.Fill to normal waterline, halfway up gauge glass.

3.Boiler water pH 7.0 to 8.5 is recommended.

4.Follow skimming procedure.

16

Part Number 550-110-639/0703

Page 16
Image 16
Weil-McLain EG manual Final adjustments, Water treatment, Filling water systems, Filling steam boilers