Weil-McLain GV90+ manual EVERY 6 MONTHS, End Of Season, User maintenance procedures continued

Models: GV90+

1 16
Download 16 pages 19.78 Kb
Page 9
Image 9
EVERY

GV90+ gas-fired water boiler — User’s Information Manual

User maintenance procedures (continued)

EVERY

6 MONTHS

Maintenance

Oil blower motor

 

Figure 4 Blower motor

1.Remove the jacket top panel to access the blower motor.

2.Use only Anderol 465. DO NOT use household universal oils.

Use only Anderol 465 to lubricate the blower motor. Do not use common uni- versal household oils.

3.See Figure 4

4.Place a few drops of oil in each of the two oiler cups on the side of the blower motor.

Operate boiler relief valve

1.Before proceeding, verify that the relief valve outlet has been piped to a safe place of dis- charge, avoiding any possibility of scalding from hot water.

To avoid water damage or scalding due to valve operation, a metal discharge line must be connected to relief valve outlet and run to a safe place of disposal. This discharge line must be installed by a qualifed heating installer or service techni- cian in accordance with the instructions in the GV90+ Boiler Manual. The discharge line must be terminated so as to eliminate possibility of severe burns should the valve discharge.

2.Read the boiler pressure/temperature gauge to make sure the system is pressurized.

3.Lift the relief valve top lever slightly, allowing water to relieve through the valve and dis- charge piping.

4.If water flows freely, release the lever and allow the valve to seat. Watch the end of the relief valve discharge pipe to ensure that the valve does not weep after the line has had time to drain. If the valve weeps, lift the seat again to attempt to clean the valve seat. If the valve continues to weep afterwards, contact your qualified service technician to inspect the valve and system.

5.If water does not flow from the valve when you lift the lever completely, the valve or discharge line may be blocked. Immediately shutdown the boiler, following the lighting instructions on the inside jacket top. Call your qualified service technician to inspect the boiler and system.

END OF

SEASON

Maintenance

Follow boiler shutdown procedure

1.Follow “TO TURN OFF GAS TO APPLIANCE” on the Operating instruction on the inside of the jacket top panel.You will also find these instructions on page 12 of this manual.

2.Do not drain system unless exposure to freezing temperatures will occur.

3.Do not drain the system if it is filled with an antifreeze solution.

4.Do not shut down boilers used for domestic water heating. They must operate year-round.

Part number 550-142-055/0411

9

Page 9
Image 9
Weil-McLain GV90+ EVERY 6 MONTHS, End Of Season, User maintenance procedures continued, Maintenance, Oil blower motor