DCA-600SSK— GENERATOR START-UP PROCEDURE (MANUAL)

DCA-600SSK— GENERATOR START-UP PROCEDURE (MANUAL)

14.The engine oil pressure gauge (Figure 54) will indicate the oil pressure (kg/ cm2) of the engine. Under normal operating conditions the oil pressure is approximately

17.Place the main, GFCI, and aux. circuit breakers in the “ON” position (Figure 57).

4

8

0 kg/cm2

ENGINE OIL PRESSURE

Figure 54. Oil Pressure Gauge

15.The coolant temperature gauge (Figure 55) will indicate the coolant temperature. Under normal operating conditions the coolant temperature should be between 165 and 215 degrees Fahrenheit (Green Zone).

Figure 57. Main, Aux. and GFCI Circuit Breakers (ON)

WATER TEMP

18.Observe the generator's ammeter (Figure 58) and verify it reads the anticipated amount of current with respect to the load. The ammeter will only display a current reading if a load is in use.

Figure 55. Coolant Temperature Gauge

16.The tachometer gauge (Figure 56) will indicate the speed of the engine when the generator is operating. Under normal operating conditions this speed is approximately 1800 RPM’s.

Figure 58. Ammeter (Load)

19. The generator will run until manually stopped or an abnormal condition occurs.

Figure 56. Engine Tachometer Gauge

DCA-600SSK — OPERATION AND PARTS MANUAL (STD)— REV. #7 (04/30/10) — PAGE 47