Circuit Breakers

Circuit Breakers

To protect the generator from an overload, a 3-pole, 800 amp, main circuit breaker is provided to protect the UVWO output terminals from overload. In addition two single-pole, 20 amp GFCI circuit breakers are provided to protect the GFCI receptacles from overload.Three 50 amp load circuit breakers have also been provided to protect the auxiliary receptacles from overload. Make sure to switch ALL circuit breakers to the "OFF" position prior to starting the engine.

Lubrication Oil

Fill the engine crankcase with lubricating oil through the filler hole, but DO NOT overfill. Make sure the generator is level. Also verify that the oil level is maintained between the two notches (Figure 30) on the dipstick. See Table 11 for proper selection of engine oil.

DCA-600SSKPRE-SETUP

Fuel Check

DANGER - EXPLOSION/FIRE HAZARDS

Fuel spillage on a hot engine can cause a fire or explosion. If fuel spillage occurs, wipe up the spilled fuel completely to prevent fire hazards. NEVER smoke around or near the generator.

REFILLING THE FUEL SYSTEM

CAUTION - REFUELINGTHE GENERATOR

ONLY properly trained personel who have read and understand this section should refill the fuel tank system.

Figure 30. Engine Oil Dipstick

When checking the engine oil, be sure to check if the oil is clean. If the oil is not clean, drain the oil by removing the oil drain plug, and refill with the specified amount of oil as outlined in the Komatsu Engine Owner's Manual. Oil should be warm before draining.

Other types of motor oils may be substituted if they meet the following requirements:

API Service Classification CH-4

API Service Classification CG-4

API Service Classification CF-4

ACEA Specification E3

ACEA Specification E2

The DCA600SSK series generators may (if equipped with a trailer or skid) have a double fuel tank system (Figure 31), which consists of an internal generator fuel tank, and a trailer mounted fuel tank. It is also possible the generator can be equipped with a skid mounted fuel tank (Figure 32). The skid type fuel system does not use the internal generator fuel tank.

Use the instructions in this section that applies to your type of fuel tank system.

ALWAYS fill the fuel tank with clean and fresh #2 diesel fuel. DO NOT fill the fuel tanks beyond their capacities.

Pay attention to the fuel tank capacity when replenishing fuel. The fuel tank cap must be closed tightly after filling. Handle fuel in a safety container. If the container does not have a spout, use a funnel. Wipe up any spilled fuel immediately.

Table 11. Recommended Motor Oil

Temperature

Type Oil

Range

 

14oF ~ 50oF

SAE 10W

(-10oC ~ 10oC)

 

32oF and above

SAE30 or SAE 10W-30

(0oC and above

Figure 31 Double Fuel Tank System

 

PAGE 40 — DCA-600SSK — OPERATION AND PARTS MANUAL (STD) — REV. #7 (04/30/10)