DCA-600SSK — OUTPUT TERMINAL PANEL CONNECTIONS

DCA-600SSK — OUTPUT TERMINAL PANEL CONNECTIONS

3Ø-480V UVWO Terminal Output Voltages

1.Jumper the voltage change-over board for 480V operation as shown in Figure 26.This configuration uses 6 jumper plates in 3 different positions. Remember there are 2 jumper plates at every position. Every jumper plate must be used.

1Ø-480V UVWO Terminal Output Voltages

1.Make sure the voltage change-over board is jumpered for 480V operation as shown in Figure 26.

2.Connect the load wires to the UVWO terminals as shown in Figure 28.

Figure 26. Voltage Change-Over Board

480V Configuration

2.Connect the load wires to the UVWO terminals as shown in Figure 27.

Figure 27. UVWO Terminal Lugs

3Ø-480V Connections

ALWAYS make sure that the

NOTEconnections to the UVWO terminals are secure and tight. The possibility of arcing exists, that could cause a fire.

Figure 28. UVWO Terminal Lugs

1Ø-480V Connections

1Ø-277V UVWO Terminal Output Voltages

1.Make sure the voltage change-over board is jumpered for 480V operation as shown in Figure 26.

2.Connect the load wires to the UVWO terminals as shown in Figure 29.

Figure 29. UVWO Terminal Lugs

1Ø-277V Connections

DANGER - UVWO OUTPUT TERMINALS

NEVER attempt to connect a load to the UVWO output terminals while the generator is operating.The possibility exists of serious injury, electrical shock, electrocution even death.

DCA-600SSK — OPERATION AND PARTS MANUAL (STD)— REV. #7 (04/30/10) — PAGE 39

Page 39
Image 39
Multiquip operation manual DCA-600SSK - OUTPUT TERMINAL PANEL CONNECTIONS, 3Ø-480V UVWO Terminal Output Voltages