DCA-600SSK — OUTPUT TERMINAL PANEL OVERVIEW

DCA-600SSK — OUTPUT TERMINAL PANEL OVERVIEW

Connecting Loads

Loads can be connected to the generator by the UVWO terminal lugs or the convenience receptacles. (See Figure 13). Make sure to read the operation manual before attempting to connect a load to the generator.

To protect the UVWO output terminals from overload, a 3- pole, 1,600 amp, main circuit breaker is provided. Make sure to switch ALL circuit breakers to the "OFF" position prior to starting the engine.

Over Current Relay

An over current relay (Figure 14) is connected to the main circuit breaker. In the event of an overload, both the circuit breaker and the over current relay may trip. If the circuit breaker can not be reset, the reset button on the over cur- rent relay must be pressed. The over current relay is lo- cated in the control box.

Figure 14. Over Current Relay

Maximum Power Output (KW)

The entire load connected to the UVWO output terminal lugs, duplex and auxiliary receptacles must not exceed 528 kW in standby or 480 kW in prime output.

Figure 13. Connecting Loads