Multiquip DCA-600SSK - GENERATOR OUTPUTS, Generator Ampere Ratings - 3Ø, Generator Amperage

Models: DCA-600SSK

1 116
Download 116 pages 26.58 Kb
Page 36
Image 36
DCA-600SSK — GENERATOR OUTPUTS

DCA-600SSK — GENERATOR OUTPUTS

Generator OutputVoltages

A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by apply- ing jumpers (6) to the voltage change-over board (Figure 15). To obtain some of the voltages as listed in Table 7 (see below) will require a fine adjustment using the voltage regu- lator (VR) control knob located on the control panel.

Voltage Change-Over Board

The voltage change-over board (Figure 15) is located on the control box, behind the generator control panel. This board has been provided for ease of voltage selection.

Generator Amperage

Tables 8 and 9 describe the generator’s current output capa- bility for both 1Ø-phase and 3Ø phase applications.

Table 8. Generator Ampere

Ratings — 1Ø

kW

139V240V277V480V

40

288

167

144

83

 

 

 

 

 

80

576

333

289

167

120

863

500

433

250

 

 

 

 

 

160

1,151

667

578

333

200

1,439

833

722

417

 

 

 

 

 

240

1,727

1,000

866

500

280

2,014

1,167

1,011

583

 

 

 

 

 

320

2,302

1,333

1,155

667

 

 

 

 

 

360

2,590

1,500

1,300

750

 

 

 

 

 

400

2,878

1,667

1,444

833

 

 

 

 

 

440

3,165

1,833

1,588

917

 

 

 

 

 

480 (max)

3,453

2,000

1,733

1,000

 

 

 

 

 

Figure 15. Voltage Change-Over Board

240V Configuration

DANGER - CHANGING JUMPER PLATES

NEVER attempt to place jumper plates on the voltage change-over board while the generator is in operation.There exists the possibility of electrocution, electrical shock or burn, which can cause severe bodily harm or even death!

Table 7. Generator Available Voltages

Three-Phase

208V

220V

240V

416V

440V

480V

 

 

 

 

 

 

 

Single-Phase

120V

127V

139V

240V

254V

277V

 

 

 

 

 

 

 

Table 9. Generator Ampere

Ratings — 3Ø

kW

240V

480V

 

 

 

40

120

60

 

 

 

80

241

120

 

 

 

120

361

180

 

 

 

160

481

241

 

 

 

200

601

301

 

 

 

240

722

361

 

 

 

280

842

421

 

 

 

320

962

481

 

 

 

360

1,083

541

 

 

 

400

1,203

601

 

 

 

440

1,323

662

 

 

 

480(max)

1,443

722

 

 

 

PAGE 36 — DCA-600SSK — OPERATION AND PARTS MANUAL (STD) — REV. #7 (04/30/10)

Page 36
Image 36
Multiquip DCA-600SSK - GENERATOR OUTPUTS, Generator Ampere Ratings - 3Ø, Generator Available Voltages, 240V, 480V, 139V