DCA-600SSK — GENERATOR OUTPUTS
Generator OutputVoltages
A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by apply- ing jumpers (6) to the voltage
Voltage Change-Over Board
The voltage
Generator Amperage
Tables 8 and 9 describe the generator’s current output capa- bility for both
Ratings — 1Ø
kW | 139V | 240V | 277V | 480V |
40 | 288 | 167 | 144 | 83 |
|
|
|
|
|
80 | 576 | 333 | 289 | 167 |
120 | 863 | 500 | 433 | 250 |
|
|
|
|
|
160 | 1,151 | 667 | 578 | 333 |
200 | 1,439 | 833 | 722 | 417 |
|
|
|
|
|
240 | 1,727 | 1,000 | 866 | 500 |
280 | 2,014 | 1,167 | 1,011 | 583 |
|
|
|
|
|
320 | 2,302 | 1,333 | 1,155 | 667 |
|
|
|
|
|
360 | 2,590 | 1,500 | 1,300 | 750 |
|
|
|
|
|
400 | 2,878 | 1,667 | 1,444 | 833 |
|
|
|
|
|
440 | 3,165 | 1,833 | 1,588 | 917 |
|
|
|
|
|
480 (max) | 3,453 | 2,000 | 1,733 | 1,000 |
|
|
|
|
|
240V Configuration
DANGER - CHANGING JUMPER PLATES
NEVER attempt to place jumper plates on the voltage
Table 7. Generator Available Voltages
208V | 220V | 240V | 416V | 440V | 480V | |
|
|
|
|
|
|
|
120V | 127V | 139V | 240V | 254V | 277V | |
|
|
|
|
|
|
|
Table 9. Generator Ampere
Ratings — 3Ø
kW | 240V | 480V |
|
|
|
40 | 120 | 60 |
|
|
|
80 | 241 | 120 |
|
|
|
120 | 361 | 180 |
|
|
|
160 | 481 | 241 |
|
|
|
200 | 601 | 301 |
|
|
|
240 | 722 | 361 |
|
|
|
280 | 842 | 421 |
|
|
|
320 | 962 | 481 |
|
|
|
360 | 1,083 | 541 |
|
|
|
400 | 1,203 | 601 |
|
|
|
440 | 1,323 | 662 |
|
|
|
480(max) | 1,443 | 722 |
|
|
|
PAGE 36 —