DCA-600SSK —TROUBLESHOOTING (MPEC)

DCA-600SSK —TROUBLESHOOTING (MPEC)

Use Table 22 (Engine Controller Troubleshooting) as a basic guideline for troubleshooting the MPEC. If the problem cannot be remedied, consult our company's business office or service plant.

TABLE 22. ENGINE CONTROLLER TROUBLESHOOTING (MPEC)

Sympton

Possible Cause

Solution

 

 

 

 

Low oil level?

Fill oil level.

 

 

 

Low oil pressure light

Oil pressure sending unit failure?

Replace oil pressure sending unit.

 

 

is on.

Time delay malfuntion in Controller?

Refer to dealer.

 

 

 

 

 

Wire shorted?

Inspect/repair wire.

 

 

 

 

Low coolant level?

Fill coolant level.

Low coolant level light

 

 

Sending unit failure?

Replace sending unit.

is on.

 

 

 

Low battery voltage?

Replace/charge battery.

 

 

 

 

Fan belt tension incorrect?

Tighten/replace fan belt.

 

 

 

 

Air flow is not circulation through radiator?

Clean/repair radiator grill.

 

 

 

 

Doors open?

Close doors.

 

 

 

High coolant

Exhaust leaking?

Replace/repair gaskets or faulty part.

 

 

temperture light is on.

Generator being overloaded?

Check/reduce load.

 

 

 

 

 

Thermostat failure?

Replace thermostat.

 

 

 

 

Air intake blocked?

Clear all air intakes.

 

 

 

 

Temperature switch failure?

Replace temperature switch.

 

 

 

Overcrank light is on.

No or low Fuel?

Fill fuel level.

 

 

Controller needs to be calibrated?

Refer to dealer.

 

 

 

 

 

RPM engine speed too high?

Adjust RPM.

 

 

 

Overspeed light is on.

Governor actuator needs to be adjusted?

Adjust governor actuator.

 

 

Governor controller needs to be adjusted?

Adjust governor controller.

 

 

 

 

 

Engine Controller needs to be calibrated?

Refer to dealer.

 

 

 

Loss of MPU light(s) or

Magnetic pick up out of adjustment?

Adjust magnetic pick up.

on.

Magnetic pick up dirty?

Clean magnetic pick up.

 

 

 

 

DCA-600SSK — OPERATION AND PARTS MANUAL (STD)— REV. #7 (04/30/10) — PAGE 69