Outdoor Installation

Install the generator in a area that is free of debris, bystanders, and overhead obstructions. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.

CAUTION - EXHAUST HAZARD

Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

Indoor Installation

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside.The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

Mounting

The generator must be mounted on a solid foundation (such as concrete) and set firmly on the foundation to isolate vibration of the generator when it is running. The generator must set at least 6 inches above the floor or grade level (in accordance to NFPA 110, Chapter 5-4.1). DO NOT remove the metal skids on the bottom of the generator. They are to resist damage to the bottom of the generator and to maintain alignment.

DCA-600SSK — INSTALLATION

Generator Grounding

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 250-64(b) and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper - 10 AWG (5.3 mm2) or larger.

b.Aluminum - 8 AWG (8.4 mm2) or larger.

2.When grounding the generator (Figure 3) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried aminimum of 8 ft. into the ground.

When connecting the generator to any buildings electrical system

NOTEALWAYS consult with a licensed electrician.

DCA-600SSK — OPERATION AND PARTS MANUAL (STD)— REV. #7 (04/30/10) — PAGE 17

Page 17
Image 17
Multiquip operation manual DCA-600SSK Installation, Outdoor Installation, Mounting

DCA-600SSK specifications

The Multiquip DCA-600SSK is a rugged, reliable, and high-performance mobile generator that caters to a wide range of applications, from construction sites to outdoor events. Designed for durability and efficiency, the DCA-600SSK is notable for its robust construction and advanced technologies that ensure reliable power delivery.

At its core, the DCA-600SSK is powered by a reliable, fuel-efficient diesel engine. This engine not only provides consistent power output but also offers extended run times, making it ideal for long-duration use in remote locations. The generator delivers a remarkable 600 kVA of power, allowing it to support heavy machinery or multiple smaller loads simultaneously.

One of the standout features of the DCA-600SSK is its impressive sound attenuation design. The generator is enclosed in a weather-resistant, sound-attenuated housing that significantly reduces noise levels, making it suitable for use in noise-sensitive environments, such as residential areas or events.

Additionally, the DCA-600SSK is equipped with a user-friendly digital control panel that provides comprehensive monitoring capabilities. This panel includes features such as voltage and frequency regulation, along with automatic start/stop functionality, which enhances both ease of use and operational efficiency. The digital display allows operators to monitor critical parameters at a glance, ensuring optimal performance and safety.

The generator is also designed with mobility in mind. It comes with forklift pockets and lifting hooks, making it easy to transport and relocate. This portability ensures quick setup and deployment, which is especially advantageous in dynamic job sites or temporary power needs.

Another important characteristic of the DCA-600SSK is its dual-frequency capability. It can operate at either 50 Hz or 60 Hz, making it versatile for international applications. This adaptability enables users to utilize the generator in various regions without modifying equipment or loads significantly.

Finally, safety features are paramount in the design of the DCA-600SSK. It includes fully automatic safety shutdowns for low oil pressure, high coolant temperature, and overload protection, safeguarding the generator from potential damage and ensuring dependable performance in demanding conditions.

In summary, the Multiquip DCA-600SSK is a powerhouse generator combining high performance, advanced technology, and user-centric design. Its efficiency, portability, and durability make it an excellent choice for professionals seeking reliable power solutions in various settings.