Multiquip operation manual DCA-600SSK - OUTPUT TERMINAL PANEL OVERVIEW, 120VAC GFCI Receptacles

Models: DCA-600SSK

1 116
Download 116 pages 26.58 Kb
Page 33
Image 33
DCA-600SSK — OUTPUT TERMINAL PANEL OVERVIEW

DCA-600SSK — OUTPUT TERMINAL PANEL OVERVIEW

120VAC GFCI Receptacles

There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R) recepacles provided on the output terminal panel. These receptacles can be accessed in any voltage change-over board position. Each receptacle is protected by a 20 amp circuit breaker. These breakers are located directly above the GFCI receptacles. Remember the load output (current) of both GFCI receptacles is dependent on the load requirements of the UVWO terminals.

Pressing the reset button resets the GFCI receptacle after being tripped. Pressing the "Test Button" (See Figure 9) in the center of the receptacle will check the GFCI function. Both receptacles should be tested at least once a month.

Each auxiliary receptacle is protected by a 50 amp circuit breaker.These breakers are located directly above the GFCI receptacles. Remember the load output (current) on all three receptacles is dependent on the load requirements of the UVWO terminals.

Turn the voltage regulator control knob (Figure 11) on the control panel to obtain the desired voltage.Turning the knob clockwise will increase the voltage, turning the knob counter- clockwise will decrease the voltage.

Figure 9. G.F.C.I. Receptacle

Twist Lock Dual Voltage 240/139 VAC Receptacles There are three 240/139 VAC, 50 amp auxiliary twist-lock(CS-6369) receptacles (Figure 10) provided on the output terminal panel. These receptacles can be accessed in any voltage change-over board position.

Figure 11. Voltage Regulator Control Knob

Access to UVWO Terminals

The UVWO terminal lugs are protected by a terminal cover (Figure 12). Un-lock the locking latch, and lift the terminal cover to gain access to the UVWO terminals.

After the load wires have been securely attached to the UVWO terminals, place the terminal cover in the down position and secure the locking latch.

Figure 12. Terminal Cover (UVWO Terminals)

Figure 10. 240/139 VAC Twist-Lock

Auxiliary Receptacles

DCA-600SSK — OPERATION AND PARTS MANUAL (STD)— REV. #7 (04/30/10) — PAGE 33