Multiquip DCA-600SSK - GENERATOR OUTPUTS/GAUGE READING, Generator Maximum Amps, Model

Models: DCA-600SSK

1 116
Download 116 pages 26.58 Kb
Page 37
Image 37
DCA-600SSK — GENERATOR OUTPUTS/GAUGE READING

DCA-600SSK — GENERATOR OUTPUTS/GAUGE READING

Maximum Amps

Table 10 shows the maximum amps the generator can pro- vide. DO NOT exceed the maximum amps as listed.

Table 10. Generator Maximum Amps

ModelDCA600SSK

 

 

Rated Voltage

Maximum Amps

 

 

Single Phase

1,333.3 amps (4 wire)

120 Volt

 

 

 

Single Phase

666.7 amps (4 wire)

240 Volt

 

 

 

Three Phase

1.443 amps

240 Volt

 

 

 

Three Phase

721.7 amps

480 Volt

 

 

 

Figure 17. AC Voltmeter

Figure 18 AC Voltmeter

Change-Over Switch

Gauge

 

(Volt reading on W-U Lug)

How to Read the Output Terminal Gauge.

The AC ammeter and AC voltmeter change-over switches on the control panel DO NOT effect the generator output. They are provided to help observe how much power is being supplied, produced at the UVWO terminals lugs.

When the voltage change-over board is jumpered for 3Ø, 240V operation (See Figure 16), place the AC Voltmeter Change-Over Switch (Figure 17) to the W-U position and the AC Ammeter Change-Over Switch (Figure 19) to the U or W position to read the output on the selected leg.

Figure 19. AC Ammeter

Change-Over Switch

40

2060

0

75

A

Figure 20. AC Ammeter (Amp reading on U lug)

NOTE

The ammeter and voltmeter

gauges are only active when the

 

UVWO terminals are in use.

Figure 16. Voltage Change-Over Board

240V Configuration

DCA-600SSK — OPERATION AND PARTS MANUAL (STD)— REV. #7 (04/30/10) — PAGE 37

Page 37
Image 37
Multiquip DCA-600SSK - GENERATOR OUTPUTS/GAUGE READING, Maximum Amps, How to Read the Output Terminal Gauge, Model