DCA-600SSK — GEN. START-UP PROCEDURE (MANUAL)
BEFORE STARTING
CAUTION - LETHAL EXHAUST HAZARD
The engine's exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating. Direct exhaust away from nearby personnel.
If applicable perform the following:
Apply commercial power to the internal battery charger receptacle (to ensure good starting) via commercial power. An external power cord will be required.This capability is an option.
Apply commercial power to the jacket water heater receptacle (not necessary for warm climates) via commercial power.An external power cord will be required.This capability is an option.
Generator and Control Panel
WARNING - STARTINGTHE GENERATOR
NEVER! manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.
1.Place the main,G.F.C.I. and aux. circuit breakers (Figure 42) in the “OFF” position prior to starting the engine.
Figure 42. Main, Aux. and GFCI
Circuit Breakers (OFF)
2.Connect the load to the UVWO terminals or auxiliary receptacles as shown in Figure 43. These load connection points can be found on the output terminal panel. To gain access to the UVWO terminals or other power receptacles, unlock the access cover and lift the door.
3.Tighten the UVWO terminal nuts securely to prevent load wires from slipping out.
Steps 1 thru 19 are referenced
for Engine Operating Panel up
NOTEto S/N 3698616. See Figure 41 below.This unit has an ignition switch and a throttle handle.
Figure 43. Load Connections
4. Close all engine enclosure doors (Figure 44).
Figure 41. Engine Operating Panel
Up To S/N 3698616