PFG Series 7 Gas-fired Water Boiler — Boiler Manual

Boiler piping connections to the heating

4. Expansion tank installations.

system (refer to piping diagrams, Page 7)

a) Closed type expansion tanks - connect from the ¾” N.P.T.

 

Failure to properly pipe the boiler may result in

expansion tank tapping on the left end section (located just

 

behind the supply outlet tapping) to the expansion tank using

 

improper operation and damage to the boiler or

¾” N.P.T. piping. Any horizontal expansion tank piping must

 

building.

pitch upward toward the tank at least 1 inch for each 5 feet of

These boilers are provided with built-in air elimination sys-

piping.

b) Diaphragm type expansion tank - may be located anywhere in

tems.

1. Install relief valve vertically in top ¾” tapping in right end section.

the system, preferably near the boiler.

 

A manual or automatic type air vent must be

 

See WARNING following.

 

 

installed in the ¾”N.P.T. tapping when a diaphragm

 

 

To avoid water damage or scalding due to relief

 

 

 

type tank is used.

 

valve operation:

The most common cause of lime deposits in boilers is inadequate

• Discharge line must be connected to relief valve

expansion tank volume. If the expansion tank is too small, system

 

outlet and run to a safe place of disposal. Terminate

water is lost from the relief valve and make-up water is added

 

the discharge line to eliminate possibility of severe

through the fill valve. Eventual section failure will result.

 

burns should the valve discharge.

5. Connect the system supply piping to the supply outlet tapping on

• Discharge line must be as short as possible and be

the left end of the boiler. See Figure 2a for minimum pipe size.

 

the same size as the valve discharge connection

6. Connect the system return piping to the return tapping on the right

 

throughout its entire length.

end of the boiler. See Figure 2a for minimum pipe size.

• Discharge line must pitch downward from the valve

7. Install drain valve provided with boiler on left side. The installer

 

and terminate at least 6”above the floor drain where

must provide a drain cock to drain the right (return) side of the

 

any discharge will be clearly visible.

boiler and its connecting piping. The drain cock on the left side of

• The discharge line shall terminate plain, not thread-

the boiler will not fully drain the right side.

8. Low water cut off:

 

ed, with a material serviceable for temperatures of

 

375 °F or greater.

a) Must be installed on any PFG boiler if the boiler is located above

• Do not pipe the discharge to any place where freez-

radiation level.

 

ing could occur.

b) Must be installed on all PFG-8 boilers to meet ASME specifica-

• No shutoff valve shall be installed between the

tions (low water cut-off not supplied by Weil-McLain).

c) May be required by certain state, local or territorial codes or

 

relief valve and boiler, or in the discharge line. Do

 

not plug or place any obstruction in the discharge

insurance companies.

 

line.

If a low water cut-off is required, use a control designed especially

• Failure to comply with the above guidelines could

for water installations. An electrode probe type low water cut-off

 

result in failure of the relief valve to operate, result-

may be located in a tee in the supply line above the boiler.

 

9. If the system is to be ASME inspected and approved, an additional

 

ing in possibility of severe personal injury, death or

 

substantial property damage.

high temperature limit is needed. Purchase and install the control

• Test the operation of the valve after filling and pres-

in the supply outlet piping to the boiler.

 

 

 

 

 

 

surizing system by lifting the lever. Make sure the

 

 

 

 

 

 

valve discharges freely. If the valve fails to operate

 

 

 

 

 

Figure 2a Minimum recommended pipe sizes

 

correctly, replace it with a new relief valve.

 

 

(Supply and return sizes refer to minimum size of

2. Install pressure-temperature gauge in tapping provided in left end

 

 

pipe connected to the boiler for 20°F temperature

section.

 

 

drop between supply and return.)

3. This boiler is for forced hot water circulation only. The circulator and

 

 

 

 

 

 

expansion tank must be selected and sized according to the design

 

 

 

 

 

 

 

 

 

 

requirements of the system.

 

 

 

 

 

 

 

 

 

 

a) Size and install circulator. Can be installed on supply or return

 

 

 

 

 

piping

 

 

 

 

 

 

 

 

 

 

b) Size expansion tank to handle the volume of water in the sys-

 

 

 

 

 

 

 

 

 

 

tem.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Part Number 550-110-641/0605

Page 6
Image 6
Weil-McLain PFG-7 manual Boiler piping connections to the heating