Ratings
SGO-W GOLD OIL WATER BOILER RATINGS (1)
|
|
|
|
|
|
|
| ROUND |
| DRAFT |
| I=B=R |
| NET | DOE | MINIMUM | FLUE | BOILER | LOSS | ||
BOILER | BURNER | DOE HEATING | I=B=R | SEASONAL | I=B=R CHIMNEY | OUTLET | WATER | THRU | ||
MODEL | CAPACITY | CAPACITY (4) | RATINGS | EFFICIENCY % |
|
|
| SIZE | CONTENT | BOILER |
RECT | ROUND | HEIGHT | ||||||||
NUMBER | GPH (3) | MBH (2) | (5) | AFUE | IN | IN | FT | IN (7) | GAL | IN W.C. (8) |
|
|
|
|
|
|
|
|
|
|
|
* * | 0.95 | 115 | 100 | 85.3 | 8 x 8 | 6 | 15 | 7 | 14.6 | .020 |
|
|
|
|
|
|
|
|
|
|
|
1.20 | 145 | 126 | 85.0 | 8 x 8 | 6 | 15 | 7 | 16.3 | .010 | |
|
|
|
|
|
|
|
|
|
|
|
1.45 | 175 | 152 | 85.0 | 8 x 8 | 7 | 15 | 7 | 18.8 | .015 | |
|
|
|
|
|
|
|
|
|
|
|
1.75 | 212 | 184 | 85.0 | 8 x 8 | 7 | 15 | 7 | 21.2 | .015 | |
|
|
|
|
|
|
|
|
|
|
|
2.00 | 242 | 210 | 85.0 | 8 x 8 | 8 | 15 | 7 | 23.7 | .015 | |
|
|
|
|
|
|
|
|
|
|
|
2.30 | 266 (6) | 231 | — | 8 x 12 | 8 | 20 | 7 | 26.2 | .025 | |
|
|
|
|
|
|
|
|
|
|
|
2.55 | 295 (6) | 257 | — | 8 x 12 | 8 | 20 | 7 | 28.6 | .030 | |
|
|
|
|
|
|
|
|
|
|
|
* * Available only as an “A” unit. “A” boiler only for use with approved burners as listed with I=B=R.
(1)
(2)MBH refers to thousands of Btu per hour.
(3)Based on 140,000 Btu/gal.
(4)Based on standard test procedures prescribed by the United States Department of Energy at combustion condition of 13.5% CO2 and
(5)Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and
(6)I=B=R gross output.
(7)See page 10 for minimum breeching diameter.
(8)Listed draft losses are for