Wells F-85, F-1725, F-101 INSTALLATION continued, WARNING Electric Shock hazard, Risk of Damage

Models: F-85 F-55 STS F-101 F-1725

1 14
Download 14 pages 16.82 Kb
Page 7
Image 7
INSTALLATION (continued)

INSTALLATION (continued)

WARNING: Electric Shock hazard

All servicing requiring access to non-insulated electrical components must be performed by a factory authorized technician.

DO NOT open any access panel which requires the use of tools. Failure to follow this warning can result in severe electrical shock.

IMPORTANT: Refer to the General Layout Data packed with the fryer for wire size requirements and other installation data.

F-55 STS FRYER ELECTRICAL INSTALLATION

F-55 fryers must be connected directly to an appropriately sized electric circuit. Conduit and strain relief must be provided by the electrician. F-55 fryers require a 208VAC or 240VAC 20 amp three-phase circuit with ground.

Raise the element head, remove the frypot and the cover at the inside rear of the fryer to gain access to the terminal block. The electrical inlet is provided by a knock-out in the rear panel.

If an equipment shutdown interface is required by local fire code, the flame sensor terminal block may be accessed by removing the cover at the inside rear of the fryer Replace the jumper of the terminal block with wiring to a normally closed contact of the building fire management system.

DO NOT connect power to the flame sensor terminal block. Wiring and contacts must be capable of handling 20 amps.

F-85 FRYER ELECTRICAL INSTALLATION

F-85 fryers must be connected directly to an appropriately sized electric circuit. Conduit and strain relief must be provided by the electrician. F-85 fryers require either a 240VAC 50 amp single phase circuit with ground; a 208VAC or 240VAC 40 amp three phase circuit with ground, or a 480VAC 20 amp three phase circuit with ground. Units are shipped from the factory wired for three phase. Conversion of 240VAC units to single phase must be performed in the field by the electrician.

Raise the element head, remove the frypot and the cover at the inside rear of the fryer to gain access to the terminal block. The electrical inlet is provided by a knock-out in the rear panel.

F-101 and F-1725 FRYER ELECTRICAL INSTALLATION

F-101 and F-1725 fryers must be connected directly to an appropriately sized electric circuit. Conduit and strain relief must be provided by the electrician. F-101 fryers require a 208VAC or 240VAC 40 amp three phase circuit with ground,

F-1725 fryers require a 208VAC or 240VAC 50 amp three phase circuit with ground, Units are shipped from the factory wired for three phase. F-101 and F-1725 fryers are not approved for conversion to single phase.

Raise the element head, remove the frypot and the cover at the inside rear of the fryer to gain access to the terminal block. The electrical inlet is provided by a knock-out in the rear panel.

CAUTION:

Risk of

Damage

DO NOT connect or energize this appliance until all installation instructions are read and followed. Damage to the appliance will result if these instructions are not followed.

CAUTION:

Electrical Shock

Hazard

The ground lug of fryers must be connected to a suitable building electric ground.

IMPORTANT:

Damage due to being connected to the wrong voltage or phase is NOT covered by warranty.

5

Page 7
Image 7
Wells F-85, F-1725, F-101, F-55 STS operation manual INSTALLATION continued, WARNING Electric Shock hazard, Risk of Damage