Westinghouse 30-471 (E) 30-471 E, Replacing Parts, Do Not Interchange Any Relay With Any Others

Models: 30-471 (E)

1 14
Download 14 pages 32.08 Kb
Page 13
Image 13

Instruction Leaflet

30-471 (E)

Page 13

Replacing Parts

The Robonic Automatic Transfer Switch has been designed to have all components accessible and readily removable from the front of the panels. The Robonic Transfer Switch is divided into two basic sections. The upper section consists of the main contacts and transfer mechanism, the lower section consisting of all the automatic control devices.

Caution

When replacing any parts of the mechanism, control transformers or breakers, isolate the Robonic Transfer Switch from any possible source of power.

To remove the transfer mechanism of the LRO transfer switch, first open the cover and remove the slide pin from the operating cam, then remove the centre bolt, the mechanism will lift straight off. The breakers and transfer motor bracket are held by four screws for ease of removal and replacement. When replacing the mechanism, first set it on the Robonic with the breaker handles in the holes provided and then fasten the centre bolt reasonably tight with the mechanism fully movable with an equivalent swing distance up and down.

To remove the transfer mechanism of the RO transfer switch, remove the four bolts holding it, taking note of which holes the bolts were in, then lift the mechanism straight off. The breakers are held by two bolts at one end and the bus connectors on the other end. The transfer motor is mounted to the transfer mechanism cover and centre drive gear. When replacing any part of the transfer mechanism, be sure that the scribe lines of the gears are in a straight row (example shown on page 6).

To prevent operation of the transfer switch while replacing mechanism or components, disconnect all sources of power.

When replacing the mechanism move it about until the breaker toggles fit between the mechanism fingers and then fasten the bolts tightly. To test for proper operation first operate manually and then connect 120 volt, 60 Hertz supply to motor leads and observe operation for free movement and proper breaker operation.

The PRO transfer switch mechanism is similar to the RO with the exception that the PRO mechanism has five gears and is mounted horizontally. The breakers are fastened to the panel by six bolts.

All Robonic transfer switch breakers and mechanisms have allowed some adjustments for mounting to assure proper operation without slipping or binding. Be sure all hardware is tightened sufficiently before re-energizing any transfer switch.

To replace any of the octal plug-ins relays, pull old units straight out and insert the replacement unit. Due to the tight fit of the receptacle and pins, you may have to move the relay about a little to pull it out.

DO NOT INTERCHANGE ANY RELAY WITH ANY OTHERS.

To replace any solid state logic modules, pull straight out and insert the replacement unit.

Parts List

 

 

 

Part Name

Style No.

 

Parts Common to Robonic II

 

 

Plug-in Modules

 

 

 

Timer,1-60 sec. adjustable, for TDEN,TDEC,TDNE

1275C74G01

Timer,0.1-10 min. adjustable, for TDEN,TDEC,TDNE

1275C74G01

Timer,0.2-30 min. adjustable, for TDEN,TDEC,TDNE

1275C74G03

Timer, 5 min. adjustable, for TDEN,TDEC,TDNE

 

1275C74G08

Relay driver — used in place of timers, for

 

 

instantaneous operation

 

 

1266C77G02

Instantaneous relay, used for NR,ER and EC 1Ø

 

 

under frequency module, for “normal” or “emergency

1275C74G04

1Ø over frequency module, for “normal” or “ermergency”

1275C74G06

3Ø over voltage module, for “normal” or “emergency”

1266C79G01

1Ø over voltage module, for “normal” or “emergency”

1266C79G02

3Ø under voltage module, for “normal” or “emergency”

1266C79G03

1Ø under voltage module, for “normal” or “emergency”

1266C79G04

Blank cover, for unused module space

 

1266C77G01

Time delay relay for engine starting, 2.5s fixed

 

3152A51H01

Time delay relay for engine starting, adjustable 1-300s

688A886H11

Options

 

 

 

Plant Exerciser

 

 

688A888G01

Battery Charger 12V

 

 

1259C26G01

Battery Charger 24V

 

 

1259C26G03

4 Position s/s fixed

 

 

7070A56H01

4 Position s/s keyed

 

 

7070A56H02

Transformer Modules

Standard

Optional

600V, for LRO, RO

160D997G05

160D997G15

480V, for LRO, RO

160D997G04

160D997G14

416V, for LRO, RO

160D997G03

160D997G13

240V, for LRO, RO

160D997G02

160D997G12

208V, for LRO, RO

160D997G01

160D997G11

600V, for PRO

160D997G10

160D997G20

480V, for PRO

160D997G09

160D997G19

416V, for PRO

160D997G08

160D997G18

240V, for PRO

160D997G07

160D997G17

208V, for PRO

160D997G06

160D997G16

 

 

 

 

For Type LRO Robonic II

 

 

 

Mechanism

 

 

833C222G02

Motor Assembly

 

 

833C223G01

Motor

 

 

688A732H02

Operating Cam

 

 

688A458G01

Slide Pin

 

 

688A731H01

Limit Switch

 

 

688A747H01

 

 

 

 

For Type RO Robonic II

 

 

 

 

 

 

 

Mechanism 150 to 400A

 

 

833C226G01

Mechanism 600 to 1000A

 

 

833C226G01

Motor

 

 

688A749H01

Solenoid

 

 

688A740H01

Brake Shoe Assembly

 

 

688A738G01

Operating Cam

 

 

572B774H01

Auxiliary & Limit Switch

 

 

688A747H01

 

 

 

 

For Type PRO Robonic II

 

 

 

 

 

 

 

Mechanism

 

 

688A109G01

Motor

 

 

688A749H02

Solenoid

 

 

688A740H01

Auxiliary & Limit Switch

 

 

688A747H01

Page 13
Image 13
Westinghouse 30-471 (E) 30-471 E, Replacing Parts, Do Not Interchange Any Relay With Any Others, Parts List, Options