Trouble Shooting Guide

 

 

Symptoms

 

Possible Causes

 

 

 

 

• refusal to re-transfer to normal

 

• a voltage sensing relay did not

source upon restoration

 

energize

 

 

• emergency to normal time delay

 

 

relay has failed

 

 

• a loose control connection

 

 

 

• will not transfer to emergency

 

engine-generator did not start

source upon failure of normal

 

• generator not producing enough

source

 

 

voltage at a high enough

 

 

 

 

frequency

 

 

• a loose control connection

 

 

• normal to emergency time

 

 

delay, if supplied, has failed

 

 

• if voltage sensing modules

 

 

supplied in emergency, there

 

 

may be a failure of one

 

 

 

• transfer without a power failure

 

• a voltage sensing module has

in the normal source

 

failed

 

 

• emergency to normal time delay

 

 

has failed

 

 

 

• no time delay when there

 

• that particular time delay has

should be

 

failed

 

 

 

engine-generator starts when

 

• the engine start time delay has

the normal source has not

 

failed

failed

 

• a plant exerciser has been built

 

 

 

 

into the system

 

 

• a voltage sensing module has

 

 

failed

 

 

 

• normal source has failed and

 

• the operating cam in the

the transfer switch cycles

 

mechanism has either broken

without stopping in emergency

 

or come out of the breaker

 

 

handle

 

 

• ELS has failed to operate

 

 

 

• if the power is not available on

 

• the breakers may be complete

the load terminals with either

 

with trip units and if there has

the normal or emergency

 

been a fault on the system, the

sources available and the

 

motor circuit has been opened

transfer switch will not operate

 

by either EAS and NAS.

 

 

Correct and manually reset the

 

 

breakers in the transfer switch

 

 

 

Recommended Maintenance

1.DO NOT perform dielectric tests on the equipment with the control components in the circuit.

2.DO NOT use loctite.

3.Check lubricant in high speed bearings of the motor and the low speed bearings of the gear box. For lubrication use Dow Corning Silicon DC44 or equivalent on the high speed bearings and Aero Shell No. 6 grease or equivalent in gear box after 5000 operations.

4.Check if control components are tight in sockets.

5.Periodically inspect all terminals (load, line and control) for tightness. Retighten all bolts, nuts and accessible hardware. Clean or replace any contact surfaces which are dirty, corroded or pitted.

6.Robonics should be in clean, dry and moderately warm locations. If signs of moisture are present, dry and clean transfer switch. If there is corrosion try to clean off, if cleaning is unsuitable replace the corroded parts. Should dust and/or debris gather on the transfer switch, brush, vacuum or wipe clean. DO NOT blow dirt into breaker or terminals.

7.Test the transfer switch operation. While the Robonic is exercising, check for freedom of movement, hidden dirt or corrosion and any excessive wear on the mechanical operating parts. Clean, lubricate or replace parts where necessary.

8.Check all adjustable control components (time delay and voltage sensing relays) for correct settings.

9.If the type “RO” mechanism is removed be sure that the scribe lines on the gears are in line. When reassembling the drive mechanisms be sure that they are fastened to the correct holes in the frame and that the breaker handles are between the cam fingers (one breaker has to be on and the other off).

Note: When servicing logic control, or transformer module, disable the motor circuit

Type LRO Robonics

CAUTION

DO NOT overtighten the pivot screw inside the operating arm. This screw was correctly adjusted at the factory to provide low friction movement of the operating arm without excessive play.

DO NOT overtighten the set screw holding the operating cam on the motor shaft.