Westinghouse 30-471 (E) 30-471 E, Type, Dial Setting, Pickup, Dropout, Time Delay Modules, Blank

Models: 30-471 (E)

1 14
Download 14 pages 32.08 Kb
Page 8
Image 8
Type

Instruction Leaflet

30-471 (E)

Page 8

Both under and overfrequency cards are factory calibrated at 60 Hz. The actual values of pickup and dropout are as follows:

Type

 

Dial Setting

Pickup

Dropout

 

 

Hz

Hz

Hz

Underfrequency

60

57

 

55

Underfrequency

50

47

 

45

Overfrequency

60

63

 

65

Overfrequency

50

53

 

55

Undervoltage / Underfrequency Module

 

S#1288C58G01

Option# 5A, 26F

 

 

 

Monitors one phase of power source.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time Delay Modules

 

1-60 sec. timer

S#1275C74G01

Option#1A, 3A, 4A

0.1-10 min. timer

S#1275C74G02

Option#1B, 3B, 4B

0.2-30 min. timer

S#1275C74G03

Option#1C, 3C, 4C

5 min fixed

S#1275C74G08

Option#4D

All can be used to accomplish TDEC, and TDNE functions.

Relay Driver

S#1266C77G02

Option#1A, 1B, 1C, 3A, 3B, 3C, 4A, 4B, 4C, 4D

This card is used in place of any of the timing modules when instantaneous operation is required.

Blank

S#1266C77G01

Used to cover any unused card slots.

All Cards Mechanically Interlocked

All cards are interlocked mechanically to prevent insertion into the wrong function slot. All cards have a repeat accuracy over a 20 to

+60°C temperature change of (+ or -) 3%. Dial settings are (+ or -) 10% of indication.

After making adjustments, tighten locking screw to secure setting. Tighten mounting screws (screws are not captive).

Page 8
Image 8
Westinghouse 30-471 (E) 30-471 E, Type, Dial Setting, Pickup, Dropout, Undervoltage / Underfrequency Module, Relay Driver