Instruction Leaflet
30-471 (E)
Page 7
Table 1 — Interrupting, Closing and Withstand Rating — Robonic Type A
Robonic |
|
| rms symmetrical amperes | |
Continuous | Type | 600 Vac | 480 Vac | 120,208,240 Vac |
Rating | ||||
30 to 100 amps | LRO | 14,000 | 14,000 | 18,000 |
150 to 225 amps | RO | 22,000 | 22,000 | 25,000 |
300 to 1000 amps | RO | 22,000 | 30,000 | 42,000 |
1200 to 3000 amps | PRO | 65,000 | 65,000 | 125,000 |
Since type A Robonics employ magnetic only breakers, their interrupt- ing, closing and withstand ratings are the same value. Under fault
conditions, with it’s “normal” breaker closed, a Robonic is required to withstand the energy let through of the normal service protective device while the fault is being cleared. At the same time, should the normal voltage fall below the voltage sensing relay’s selected value, - and if the alternate source were available, the Robonic could transfer before the normal service protective device cleared the fault.
This would require that the Robonic be capable of interrupting the protective device’s let through current. In addition, the Robonic could be required to close in on a fault. Thus can be seen the need for Robonics to have, interrupting, closing and withstand ratings.
The interrupting, closing and withstand ratings shown in Table 1 are those for standard type A Robonics. For higher values, consideration can be given to use of Robonics built with Mark 75,
Table 2 — Maximum Upstream Circuit Protective Devices for
Type A Robonics, All Classes of Loads
Robonic | Maximum Upstream | Maximum Upstream | ||
|
|
| ||
Type | Continuous | Breaker Frame Size | Class | Class |
| Rating |
| J or L | K5 or R |
| (amps) |
|
|
|
LRO | 30 | EB, EHB, FB, HFB, | 100 | 100 |
LRO | 70 | EB, EHB, FB, HFB, | 100 | 100 |
LRO | 100 | FB, HFB | 100 | 100 |
RO | 150 | 225 | 225 | |
RO | 200 | DA, LBB, LB, HLB, LC, HLC, | 225 | 225 |
RO | 225 | DA, LBB, LB, HLB, LC, HLC, | 225 | 225 |
RO | 300 | DA, LBB, LB, HLB, LC, HLC, | 400 | 400 |
RO | 400 | LA, HLA, LC, HLC, | 400 | 400 |
RO | 600 | MA, HMA, MC, HMC, | 600 | 600 |
RO | 800 | NB, HNB, NC, HMC, PB, PC, | 800 | ... |
RO | 1000 | PB, PC, | 1200 | ... |
PRO | 1200 | PB, PC, | 1200 | ... |
PRO | 1400 | PB, PC | 2000 | ... |
PRO | 2000 | PB, PC | 2000 | ... |
¬ Fuse ratings given are as allowed by C.E.C. If other ratings are desired, refer to C.E.C.
Table 3 — Maximum Upstream Circuit Protective Devices for Type A Robonics, 90% or Larger Motor Load
Robonic | Maximum Upstream | Maximum Upstream | ||
|
|
| ||
Type Continuous | Breaker Frame Size | Class | Class | |
| Rating |
| J or L | K5 or R |
| (amps) |
|
|
|
LRO 30, 70, 100 | EB, EHB, FB, HFB, | 300 | 100 | |
|
|
|
| |
RO | 150,200,225 | CA,CAH,JA,KA,HKA,LA,HLL,LB, | 400 | 225 |
|
| HLB, MA, NB, HLC, MC, HMC, NC, |
|
|
|
| HNC, |
|
|
RO | 400 | LB, HLB, LC, HLC, LA, HLA, | 600 | 400 |
|
| MA,HMA,MC, HMC, NB, HNP, NC, |
|
|
|
| MNC, |
|
|
RO | 600, 800 | MA, HMA, MC, HMC, NB, MNB, NC, | 1200 | 600 |
|
| MNC, |
|
|
RO | 1000 | NB, HNB, NC, HNC, | 1200 | ... |
PRO 1200 | 1200 | ... | ||
PRO 1400, 2000 | PB, PC, | 2000 | ... |
¬ Fuse ratings given are as allowed by C.E.C. If other ratings are desired, refer to C.E.C.
Logic Control |
|
|
Voltage Sensing Modules |
| |
1Ø Undervoltage | S# 1266C79G04 | Option#5C, 26B |
3Ø Undervoltage | S# 1266C79G03 | Option#5C, 26A |
These cards are normally set at 70% dropout and 90% pickup.
1Ø Overvoltage | S# 1266C79G02 | Option#5B, 26C |
3Ø Overvoltage | S#12266C79G01 | Option#5B, 26C |
These cards are normally set at 105% pickup and 115% dropout. All styles are applicable to both emergency and normal source monitoring.
Frequency Sensing Modules |
|
| |
1Ø Underfrequency | S#1275C74G04 | Option#5D, 26D | |
1Ø Overfrequency | S#1275C74G06 | Option#5E, 26E | |
|
|
|
|
|
|
|
|