Instruction Leaflet

30-471 (E)

Page 7

Table 1 — Interrupting, Closing and Withstand Rating — Robonic Type A

Robonic

 

 

rms symmetrical amperes

Continuous

Type

600 Vac

480 Vac

120,208,240 Vac

Rating

30 to 100 amps

LRO

14,000

14,000

18,000

150 to 225 amps

RO

22,000

22,000

25,000

300 to 1000 amps

RO

22,000

30,000

42,000

1200 to 3000 amps

PRO

65,000

65,000

125,000

Since type A Robonics employ magnetic only breakers, their interrupt- ing, closing and withstand ratings are the same value. Under fault

conditions, with it’s “normal” breaker closed, a Robonic is required to withstand the energy let through of the normal service protective device while the fault is being cleared. At the same time, should the normal voltage fall below the voltage sensing relay’s selected value, - and if the alternate source were available, the Robonic could transfer before the normal service protective device cleared the fault.

This would require that the Robonic be capable of interrupting the protective device’s let through current. In addition, the Robonic could be required to close in on a fault. Thus can be seen the need for Robonics to have, interrupting, closing and withstand ratings.

The interrupting, closing and withstand ratings shown in Table 1 are those for standard type A Robonics. For higher values, consideration can be given to use of Robonics built with Mark 75, Tri-Pac or SCB breakers.

Table 2 — Maximum Upstream Circuit Protective Devices for

Type A Robonics, All Classes of Loads

Robonic

Maximum Upstream

Maximum Upstream

 

 

 

Fuse-Rating¬

Type

Continuous

Breaker Frame Size

Class

Class

 

Rating

 

J or L

K5 or R

 

(amps)

 

 

 

LRO

30

EB, EHB, FB, HFB, FB-P

100

100

LRO

70

EB, EHB, FB, HFB, FB-P

100

100

LRO

100

FB, HFB

100

100

RO

150

CA,CAH,JA,KA,HKA,LC,HLC,LA-P

225

225

RO

200

DA, LBB, LB, HLB, LC, HLC, LA-P

225

225

RO

225

DA, LBB, LB, HLB, LC, HLC, LA-P

225

225

RO

300

DA, LBB, LB, HLB, LC, HLC, LA-P

400

400

RO

400

LA, HLA, LC, HLC, NB-P

400

400

RO

600

MA, HMA, MC, HMC, NB-P

600

600

RO

800

NB, HNB, NC, HMC, PB, PC, PB-P

800

...

RO

1000

PB, PC, PB-P

1200

...

PRO

1200

PB, PC, PB-P

1200

...

PRO

1400

PB, PC

2000

...

PRO

2000

PB, PC

2000

...

¬ Fuse ratings given are as allowed by C.E.C. If other ratings are desired, refer to C.E.C.

Table 3 — Maximum Upstream Circuit Protective Devices for Type A Robonics, 90% or Larger Motor Load

Robonic

Maximum Upstream

Maximum Upstream

 

 

 

Fuse-Rating¬

Type Continuous

Breaker Frame Size

Class

Class

 

Rating

 

J or L

K5 or R

 

(amps)

 

 

 

LRO 30, 70, 100

EB, EHB, FB, HFB, FB-P

300

100

 

 

LA-P c/w 400LAP10

 

 

RO

150,200,225

CA,CAH,JA,KA,HKA,LA,HLL,LB,

400

225

 

 

HLB, MA, NB, HLC, MC, HMC, NC,

 

 

 

 

HNC, LA-P, NB-P c/w 500 NAB12

 

 

RO

400

LB, HLB, LC, HLC, LA, HLA, LA-P

600

400

 

 

MA,HMA,MC, HMC, NB, HNP, NC,

 

 

 

 

MNC, NB-P

 

 

RO

600, 800

MA, HMA, MC, HMC, NB, MNB, NC,

1200

600

 

 

MNC, NB-P

 

 

RO

1000

NB, HNB, NC, HNC, PB-P

1200

...

PRO 1200

NB,HNB,NC,HNC,PB-P

1200

...

PRO 1400, 2000

PB, PC, PB-P

2000

...

¬ Fuse ratings given are as allowed by C.E.C. If other ratings are desired, refer to C.E.C.

Logic Control

 

 

Voltage Sensing Modules

 

1Ø Undervoltage

S# 1266C79G04

Option#5C, 26B

3Ø Undervoltage

S# 1266C79G03

Option#5C, 26A

These cards are normally set at 70% dropout and 90% pickup.

1Ø Overvoltage

S# 1266C79G02

Option#5B, 26C

3Ø Overvoltage

S#12266C79G01

Option#5B, 26C

These cards are normally set at 105% pickup and 115% dropout. All styles are applicable to both emergency and normal source monitoring.

Frequency Sensing Modules

 

 

1Ø Underfrequency

S#1275C74G04

Option#5D, 26D

1Ø Overfrequency

S#1275C74G06

Option#5E, 26E

 

 

 

 

 

 

 

 

Page 7
Image 7
Westinghouse 30-471 (E) Interrupting, Closing and Withstand Rating Robonic Type a, Logic Control Voltage Sensing Modules