5 W If you must change to a three- wire, single-phase, 120/240-volt, 60-Hz, AC-only, electrical supply system, and local codes permit,
aU.L.-listed, 120/240-v0lt minimum, 30-
| ampere, | dryer | Figure 3 |
| power | supply cord |
| |
| kit with | a receptacle | of NEMA Type lo- |
30R may be used. (See Figure 3.) This cord must contain three, No.-1 0 copper conductors with ring terminals or spade terminals with upturned ends on the washer/dryer end. Where local codes permit, it must be plugged into a mating 30-ampere receptacle (NEMA Type 1O- 30R). Cord should be Type SRD or SRDT and be at least four feet long. The three-wire power supply cord is not provided with the washer/dryer. A kit, Part No. 687104, is available from your Whirlpool dealer.
NOTE: If local codes require permanently connected wiring, see “Alternate electrical connection,” Panels E and F.
To convert to three-wire electrical system, the four-wire power supply cord must be removed and the appliance cabinet must be grounded according to local codes either by using the neutral terminal or a separate grounding wire. (See “Alternate
electrical connection,” Panels E and F for detailed instructions).
Exhaust reaufrements*
Fire/Health Hazard
l Do Not use non-metal, flexible duct. l Do Not use metal duct smaller than
four inches in diameter.
l Do Not use exhaust hoods with magnetic latches.
. Check that exhaust system is not longer than specified. Exhaust systems longer than specified will: - Accumulate lint.
-Shorten the life of the dryer.
-Reduce performance, resulting in longer drying times and increased energy usage.
Failure to follow specifications may result in a fire.
l Do Not exhaust dryer into a chimney, furnace cold air duct, attic or crawl space, or any other duct used for venting.
. Clean the exhaust system every other year.
l Do Not install flexible duct in enclosed walls, ceilings or floors.
Accumulated lint could result in a fire or cause moisture damage.
. Exhausting your dryer indoors is not
recommended. The moisture and lint indoors may cause:
-FIRE HAZARD from lint collected in dryer.
-Moisture damage to woodwork, furniture, paint, wallpaper, carpet, etc.
-Housecleaning problems and possible health problems.
Failure to follow these instructions could result in fire damage or personal injury.
Four-inch rigid metal pipe is preferred. Plan installation to use the fewest number of
exhaust air flow exhaust air flow
Metal flexible duct should be fully extended and supported when the dryer is in its final position. DO NOT KINK OR CRUSH THE DUCT. The metal flexible duct must be completely open to allow adequate exhaust air to flow.
Allow as much room as possible when using elbows or making turns. Bend duct gradually to avoid kinking. Remove excess flexible duct to avoid sagging and kinking that may
result in reduced air flow.
The exhaust duct can be routed up, down, left, right or straight out the back of the washer/dryer. Space requirements are provided on Panel G of the Installation Instructions and on the
rear panel of the washer/dryer.
Maximum length of the exhaust system depends upon the type of duct used, number of elbows and the type of exhaust hood. The maximum length for both rigid and flexible duct is shown in the chart
Ii-l/i,,
Rear, Side or Bottom Exhaust
Number of 90” Turns
042 FT. MAXIMUM
134 FT. LENGTH OF
226 FT. 4” DIA. RIGID
METAL DUCT
0 26 FT. MAXIMUM
:21 FT. LENGTH OF
16 FT. 4” DIA. FLEXIBLE METAL DUCT
For exhaust systems not covered by the exhaust length chart, see Whirlpool Service Manual, Exhaustina Whirlpool Drvers, Part No. 603197, available from your Whirlpool parts distributor.
Service check: The back pressure in any exhaust system used must not exceed
0.6inches of water column measured with an incline manometer at the point that the exhaust duct connects to the dryer.
Exhausting the dryer outside is
recommended. A closet installation must be exhausted outside. Recessed installation that is not exhausted outside must use Exhaust Deflector Pat-t No. 694609 available from your Whirlpool dealer. See “Recessed and closet installation instructions,” Panel G, for adequate, unobstructed air opening requirements.
If the washer/dryer is installed in a confined area such as a bedroom, bathroom or closet, it must be exhausted to the outside and provision must be made for enough air for combustion and ventilation. Check governing codes and ordinances. Also refer to “Recessed and closet installation instructions,” Panel G.
An exhaust hood should cap the exhaust duct to prevent exhausted air from returning into
dryer. The outlet of the --lbhood must be at least
12 inches from the ground or any object that may be in the path of the exhaust.
Four-inch outlet hood is preferred. However, a 2-l/2-inch outlet exhaust hood may be used. A 2-l/2-inch outlet creates greater back pressure than other hood types.
Exhausting the dryer through the side of the washer/dryer requires the use of Side Exhaust Kit, Part No. 3391335.
Follow kit installation \ instructions for proper exhaust installation.
Mobile home installation
This appliance is suitable for mobile home installation. The installation of the washer/dryer must conform to the
Manufactured Home Construction and Safety, Title 24 CFR, Part 3280 (formerly the Federal Standard for Mobile Homes Construction and Safety, Title 24, HUD Part 280, latest edition).
Mobile home exhaust requirements: The washer/dryer must have an outside exhaust. If the dryer is exhausted
through the floor and the area under the mobile home is enclosed, the exhaust system must terminate outside the enclosed area. Extension beyond the enclosure will prevent lint and moisture build-up under the mobile home.