11
1. Prepare your 3-wire cable

for direct connection

1"
(25 mm)
3½"
(89 mm)
2. Remove center screw
B
5. Connect remaining wires
4. Connect ground wire
F
A
Use where local codes permit connecting cabinet-ground
conductor to neutral wire.
Remove center terminal block screw (B).
Direct wire cable must have 5 ft. (1.52 m) of extra length so
dryer may be moved if needed.
Strip 31/2" (89 mm) of outer covering from end of cable. Strip
insulation back 1" (25 mm). If using 3-wire cable with ground
wire, cut bare wire even with outer covering. Shape wire ends
into hooks.
Connect ground wire (green or bare) (F) of direct wire cable
under green external ground conductor screw (A). Tighten
screw.
Place hooked ends of remaining direct wire cable wires under
outer terminal block screws (hooks facing right). Squeeze
hooked ends together and tighten screws. Finally, reinsert tab
of terminal block cover into slot of dryer rear panel. Secure
cover with hold-down screw. Now, go to Venting Requirements.
3. Connect neutral wire
C
B
Place hooked end of neutral wire (white
or center) (C) of direct wire cable under
center terminal block screw (B), hook
facing right. Squeeze hooked end together.
Tighten screw.
3. Connect neutral ground wire and

neutral wire

C
E
B
Connect neutral ground wire (E) and place
hooked end (hook facing right) of neutral
wire (white or center wire) (C) of direct wire
cable under center screw of terminal block
(B). Squeeze hooked ends together and
tighten screw.

3-Wire Direct Wire Connection