Whirlpool WPDV160XS Installation Instructions, DuctworkRequirements, ElectricalRequirements

Models: WPDV160XS WPDH160XS WGDV160UH WGDH160UH

1 16
Download 16 pages 13.24 Kb
Page 5
Image 5
DuctworkRequirements

DuctworkRequirements

Install the conditioned air plenum, ducts and air filters (not provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Systems (latest edition).

For the best performance, draw air from the central part of the building and return it to the outer areas of the building.

Insulated flexible duct may be used on the discharge air supply side of the dehumidifier to reduce air noise from the fan.

Flexible duct is recommended on all connections to reduce noise and vibration transmitted to rigid ductwork in the building.

Duct Size

For supply duct lengths up to 25 ft, use a minimum of 10" diameter round or equivalent rectangular duct. For return duct lengths up to 25 ft, use a minimum of 12" diameter round or equivalent rectangular duct.

For supply duct lengths longer than 25 ft, use a minimum of 12" diameter or equivalent rectangular duct. Grilles or diffusers installed on the duct ends should not restrict airflow. For return duct lengths longer than 25 ft, use a minimum of 14" diameter round or equivalent rectangular duct.

For two or three isolated areas that do not have any heat or air conditioning ductwork, use a minimum of 8" diameter branch duct to each area.

For four or more isolated areas with stagnant air, use a minimum of 6" diameter branch duct to each area.

ElectricalRequirements

Duct SizeWARNING

Electrical Shock Hazard

Use 12 gauge solid copper wire.

Electrically ground dehumidifier.

Connect ground wire to green ground lug.

Failure to follow these instructions can result in death, fire, or electrical shock.

Recommended Grounding Method

A 110- to 120-volt, 14.5 FLA amps, 60 Hz, AC only 20-amp fused, grounded electrical supply is required.

All field wiring must be done in accordance with National Electrical Code requirements, applicable requirements of UL, or local codes, where applicable.

INSTALLATION INSTRUCTIONS

ElectricalRequirements WARNING

Fire Hazard

Read and follow all instructions provided for installation, service, alteration, or maintenance.

Failure to follow these instructions can result in death or fire.

InspectShipment

Recommended Grounding MethodWARNING

Excessive Weight Hazard

Use two or more people to move and install dehumidifier.

Failure to do so can result in back or other injury.

This whole house dehumidifier is shipped in one package, completely assembled and wired.

1.Check the dehumidifier rating plate to confirm specifications are as ordered.

2.Upon receipt of equipment, inspect it for possible shipping damage. Examine the dehumidifier inside the carton if the carton is damaged.

If damage is found, it should be noted on the carrier’s freight bill. Damage claims should be filed with the carrier immediately. Claims of shortages should be filed with the seller within 5 days.

NOTE: If any damages are discovered and reported to the carrier, do not install the dehumidifier, because your claim may be denied.