INSTALLATION REQUIREMENTS

INSTALLATION REQUIREMENTS

These instructions are intended as a general guide only for use by qualified persons and do not supersede any national or local codes in any way. Compliance with all local, state or national codes pertaining to this type of equipment should be determined prior to installation.

Read this entire instruction manual as well as instructions supplied with separate equipment before starting the installation.

The installation of the whole house dehumidifier must conform to the requirements of the National Fire Protection Association, the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States, and any state laws, local ordinances (including plumbing or wastewater codes). Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.

Install the conditioned air plenum, ducts and air filters (not provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Systems (latest edition).

The whole house dehumidifier is designed and approved for indoor use only.

It is recommended that the whole house dehumidifier be matched to the HVAC system to ensure proper operation and efficient performance.

Refer to the rating plates located on the whole house dehumidifier and on the HVAC system.

It is recommended that the whole house dehumidifier be connected to only one existing HVAC system. If there are multiple HVAC systems in the building, use one dehumidifier per system.

ToolsandParts

Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed here.

Tools Needed

Locking pliers

Screwdriver

Drill and drill bit

Tin snips

Parts Needed

Sheet metal screws or rivets

Shop-fabricated sheet metal turning vanes, offsets, and transitions, if needed

Sealant

Insulated flexible duct

³⁄₈"-16all-thread rod for suspended applications

Insulated duct for fresh air ventilation

Parts Supplied

Grommet plugs (4)

Check local codes and HVAC supplier. Check existing electrical supply, and read “Electrical Requirements” and “Location Requirements” before purchasing parts.

LocationRequirements

The dehumidifier may be installed on all new or existing furnaces or air handlers used in residential applications.

The whole house dehumidifier is designed to be located indoors.

Locate the whole house dehumidifier as close to the return air duct of an existing furnace or air handler as possible to minimize the required ductwork for connecting the dehumidifier to the existing furnace or air handler.

The location should allow for access to the filter access panel at the front of the dehumidifier for inspection and replacing the filter. See the Minimum Clearance Requirements chart.

The location must allow for access to the electrical access panel for servicing and maintenance.

Locate the whole house dehumidifier in an area where the temperature is between 40ºF (4ºC) and 125ºF (52ºC). If the dehumidifier is located in an area of extreme heat or high humidity, additional external insulation may be required to prevent condensation on the exterior of the dehumidifier.

If the dehumidifier is located above a living area or above an area where water leakage may cause damage (see local codes for other requirements), a secondary drain pan must be installed under the dehumidifier.

The controls for the whole house dehumidifier are remote from the dehumidifier and must be located in the space that is to be conditioned. The controls are low voltage (24-volt) and should be connected to the dehumidifier with code approved, low voltage thermostat cable.

If the dehumidifier is located directly on structural building members, use vibration absorbers/eliminators.

Minimum Clearance Requirements

For Optimum Service Access

Front24"

Rear12"

Blower End

12"

Top12"

2