ATTACH THERMOSTAT TO SUBBASE
IT IS RECOMMENDED THAT YOU SET OPTION SWITCHES TO DESIRED POSITION BEFORE ATTACH- ING ON SUBBASE (see OPERATION). IT IS ALSO
RECOMMENDED THAT YOU PROGRAM THE THERMOSTAT WITH BATTERY INSTALLED BEFORE ATTACHING ON SUBBASE (see OPERATION GUIDE for programming instructions).
POWER TO THERMOSTAT MUST BE OFF BEFORE
ATTACHING THERMOSTAT TO WALL. FAILURE TO
TURN OFF POWER BEFORE ATTACHING THERMO-
STAT MAY CAUSE EQUIPMENT DAMAGE DUE TO
RAPID COMPRESSOR CYCLING.
ENGAGE TWO UPPER GUIDES;
PIVOT DOWN
To attach thermostat to subbase, line up the plastic snap
guides at the top of the thermostat and the 4 connector Figure 7. Attaching thermostat to subbase pins on the thermostat with the connectors near the top
right section of the subbase (when viewed from the front). Gently pivot the thermostat down until the
OPERATION
SYSTEM CONFIGURATION
NOTE
ANY TIME AN OPTION SWITCH IS CHANGED, THE 9 VOLT ENERGIZER® BATTERY MUST BE REMOVED FOR A MINIMUM OF 2 MINUTES.
SET OPTION SWITCHES
1.Single Stage Compressor Heat Pump — with re- versing valve energized through B or O terminals
W1 |
|
| Y1 | Field jumper W1 & Y1 | |||||
|
|
|
|
|
|
|
|
| Switch #1 OFF |
ON |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| Switch #2 OFF |
|
|
|
|
|
|
|
|
| Switch #3 OFF |
1 2 | 3 4 |
| Switch #4 (see step 6) |
2.Two Compressor (Split) System
W1 |
|
| Y1 | Field jumper W1 & Y1 | |||||
W2 |
|
| Y2 | Field jumper W2 & Y2 | |||||
|
|
|
|
|
|
|
|
| Switch #1 OFF |
ON |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| Switch #2 ON |
|
|
|
|
|
|
|
|
| Switch #3 OFF |
1 2 | 3 4 |
| Switch #4 (see step 6) |
Battery | |
W18 |
|
Option switches |
Figure 8. Back of thermostat body
3.
ON |
|
|
|
|
|
|
| Switch #1 ON | |
|
|
|
|
|
|
|
|
| Switch #2 OFF |
|
|
|
|
|
|
|
|
| Switch #3 OFF |
1 2 3 4 |
| Switch #4 (see step 6) |
4.
ON |
|
|
|
|
|
|
| Switch #1 ON | |
|
|
|
|
|
|
|
|
| Switch #2 ON |
|
|
|
|
|
|
|
|
| Switch #3 (see step 5) |
1 2 3 4 |
| Switch #4 (see step 6) |
6