White Rodgers 1F95-391 Multi-Stageterminal Outputs, Heat Pump Terminal Outputs, Configuration

Models: 1F95-391

1 12
Download 12 pages 39.93 Kb
Page 3
Image 3
MULTI-STAGE TERMINAL OUTPUTS

MULTI-STAGE TERMINAL OUTPUTS

Refer to equipment manufacturers’ instruc- tions for specific system wiring information.

You can configure the thermostat for use with either multi-stage electric heat systems or multi-stage gas systems. When configured

for electric heat, the G terminal (blower/fan) will be energized on a call for heat, using the installer table (pgs. 5 & 6).

This thermostat is designed to operate a single-transformer system. If you have a two- transformer system, cut and tape off one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one transformer, the two commons must be jumpered together.

Use the terminal output information below to help you wire the thermostat properly for your multi-stage system. After wiring, see

CONFIGURATIONsection for proper thermostat configuration.

THERMOSTAT TERMINALS (Upper)

L

SA

SB

SC

OT

 

 

 

 

 

Malfunction Light

Remote Sense A

Remote Sense B

Remote Sense C

Outdoor Sensor

 

 

 

 

 

THERMOSTAT TERMINALS (Lower)

SYSTEM

C

R

HM

W2

DHM

E/W1

Y2

Y1

B

O

G

 

 

 

 

 

 

 

 

 

 

 

 

Multi-Stage

24 Volt

24 Volt

Energizes on a

Heat mode

E2/P switch in the P position,

Heat mode

Cool mode

Cool mode

Energized in Heat

Energized in

Blower/Fan

 

(Common)

(Hot)

call for heat if

2nd stage

Energizes on a call for

1st stage

2nd stage

1st stage

and Off Mode

Cool Mode

Energized on

 

 

 

Humidity setpoint is

 

Dehumidification.

 

 

 

 

 

call for Cool

 

 

 

above room

 

E2/P switch in E2 position,

 

 

 

 

 

(and Heat if

 

 

 

humidity.

 

De-energizes on a

 

 

 

 

 

configured

 

 

 

 

 

call for Dehumidification.

 

 

 

 

 

to Electric Heat).

 

 

 

 

 

 

 

 

 

 

 

 

HEAT PUMP TERMINAL OUTPUTS

Refer to equipment manufacturers’ instruc- tions for specific system wiring information.

You can configure the thermostat for use with the following heat pump system types:

HEAT PUMP TYPE

1.

Single-stage

compressor

system;

gas or electric backup.

HEAT PUMP TYPE

2.

Multi-stage or two-

compressor

system;

gas or electric backup.

This thermostat is designed to operate a single-transformer system. If you have a two- transformer system, cut and tape off one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one transformer, the two commons must be jumpered together.

Use the terminal output information below to help you wire the thermostat properly for your heat pump system type. After wiring,

see

CONFIGURATION

section for proper

thermostat configuration.

 

THERMOSTAT TERMINALS (Upper)

L

SA

SB

SC

OT

 

 

 

 

 

Malfunction Light

Remote Sense A

Remote Sense B

Remote Sense C

Outdoor Sensor

THERMOSTAT TERMINALS (Lower)

SYSTEM

C

R

HM

W2

DHM

E/W1

Y2

Y1

B

O

G

 

 

 

 

 

 

 

 

 

 

 

 

Single-stage compressor system; gas or electric backup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Pump 1

24 Volt

24 Volt

Energizes on a

Heat mode

E2/P switch in P position,

Heat mode

No Output

Heat and

Energized in Heat,

Energized in

Blower/Fan

 

(Common)

(Hot)

call for heat if

3rd stage,

Energizes on a call for

2nd stage,

 

Cool mode

Off, Emergency

Cool Mode

Energized on

 

 

 

Humidity setpoint is

Emergency Mode

Dehumidification.

Emergency Mode

 

1st stage

Mode

 

call for Heat and Cool

 

 

 

above room

2nd stage

E2/P switch in E2 position,

1st stage

 

(compressor 1)

 

 

 

 

 

 

humidity.

 

De-energizes on a

 

 

 

 

 

 

 

 

 

 

 

call for Dehumidification.

 

 

 

 

 

 

Multi-stage or two compressor system; gas or electric backup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Pump 2

24 Volt

24 Volt

Energizes on a

Emergency Mode

E2/P switch in P position,

Heat mode

Heat and

Heat and

Energized in Heat,

Energized in

Blower/Fan

 

(Common)

(Hot)

call for heat if

2nd stage

Energizes on a call for

3rd stage,

Cool mode

Cool mode

Off, Emergency

Cool Mode

 

Energized on

 

 

 

Humidity setpoint is

 

Dehumidification.

Emergency Mode

2nd stage

1st stage

Mode

 

 

 

 

 

 

call for Heat and Cool

 

 

 

above room

 

E2/P switch in E2 position,

1st stage

(compressor 2)

(compressor 1)

 

 

 

 

 

 

 

 

 

 

 

 

humidity.

 

De-energizes on a

 

 

 

 

 

 

 

 

 

 

 

call for Dehumidification.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Page 3
Image 3
White Rodgers 1F95-391 specifications Multi-Stageterminal Outputs, Heat Pump Terminal Outputs, Configuration