White Rodgers 1F95CA-391 Configuration, Switches, Reset Switch, E2/P SWITCH DHM TERMINAL FUNCTION

Models: 1F95CA-391

1 12
Download 12 pages 22.52 Kb
Page 4
Image 4
CONFIGURATION

CONFIGURATION

SWITCHES

RESET SWITCH

See the Troubleshooting section at the end of this document for more information about the function of this switch.

E2/P SWITCH (DHM) TERMINAL FUNCTION

The E2/P switch is located on the back of the thermostat body (see fig. 2). This switch controls how the DHM terminal will be energized.

1.In the P position (up) the DHM terminal will be energized on a call for dehumidification.

2.In the E2 position (down) the DHM terminal will always be energized except on a call for dehumidification. The switch must be in the E2 position on some electronically controlled variable speed blower systems.

1

S18

2

P S19

E2

1Reset switch

2E2/P switch

Figure 2. Switch locations on back of thermostat body

DEHUMIDIFICATION WIRING WITHOUT AN ELECTRONICALLY CONTROLLED VARIABLE SPEED BLOWER SYSTEM FOR SINGLE STAGE COMPRESSOR SYSTEM ONLY

If you have a single stage compressor system see the diagram below. A relay (customer provided) should be installed as shown in Fig. 5 to switch the fan speed to the next lower speed on a call for dehumidification from the thermostat. The reduction in air flow allows the coil to remove more humidity from the air. The relay should be rated for blower motor load. Since this configuration reduces the air flow in cooling, the anti- freeze-up control (White-Rodgers CAFC) or equivalent is recommended. The CAFC prevents the air conditioning coil from freezing due to low air flow, dirty filters, low refrigerant pressure, etc. The CAFC snaps onto the suction line close to the evaporator coil as possible and breaks the compressor circuit when the suction line drops below 38°F and re-make the circuit at 46°F.

NOTE: If you have a two stage compressor, the thermostat software will lengthen cycle times for the first stage of cool. The longer cycles will improve dehumidification while cooling, allowing the DHM terminal not to be used on a two stage compressor system.

Selecting P - DHM Energizes on call for

P

Dehumidification

Selecting E2 - DHM Deenergizes on call for Dehumidification

E2

R

C

Y1

G

DHM

N.C.

N.O.

Customer supplied relay rated for blower motor load

Cool Fan Speed

 

HIGH

 

MED. HIGH

3-4 speed

 

LOW

Blower

 

Motor

 

 

COMMON

 

 

 

Furnace

Speed

Control

Fan

Module

Heat

 

HOT

24VAC

NEUTRAL

120 VAC

TRANSFORMER

Figure 3. Typical Wiring for Dehumidifier System

HM

 

 

R

 

 

 

 

 

 

Relay

 

 

 

 

 

 

 

 

 

HOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90-290Q

 

 

 

 

 

 

 

 

 

 

 

 

or equivalent

24 VAC

 

 

 

 

I

 

 

NEUTRAL

120 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

Humidifier

120 VAC

 

 

NEUTRAL

 

 

 

System

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 4. Typical Wiring for 120V Humidifier System

HMR

 

 

 

 

 

 

 

 

 

 

 

 

Humidifier

 

 

 

 

 

 

 

 

 

 

System

24 VAC

 

 

 

 

I

 

 

HOT

120 VAC

 

 

 

 

 

 

 

 

NEUTRAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

Figure 5. Typical Wiring for 24V Humidifier System

4

Page 4
Image 4
White Rodgers 1F95CA-391 specifications Configuration, Switches, Reset Switch, E2/P SWITCH DHM TERMINAL FUNCTION