CHECK THERMOSTAT OPERATION

CHECK THERMOSTAT OPERATION

FAN OPERATION

If your system does not have a G terminal Connection, skip to HEATING SYSTEM section below.

1.Turn power on to the system.

2.Press PROGRAM RUN .

3.

Press

FAN

until FAN ON is displayed.

 

The fan should begin to operate.

4.

Press

FAN

until FAN AUTO is

 

displayed. The fan should stop operating.

HEATING SYSTEM

1.Press PROGRAM RUN .

2.Press SYSTEM until HEAT is displayed. If the heating system has a standing pilot, ensure that it is lit.

3.Press the FAN OPERATION to adjust thermostat setting above room temperature. The

heating system should begin to operate.

4.Press the 2.Press PROGRAM RUN . to adjust thermostat setting below room temperature. The

heating system should stop operating.

COOLING SYSTEM

!CAUTION

To prevent compressor and/or property damage, if the outdoor temperature is below 50°F (10°C), DO NOT operate the cooling system.

1.Press the PROGRAM RUN .

2.Press SYSTEM until COOL is displayed.

3.Press until FAN AUTO is to adjust thermostat setting below room temperature. The fan should

come on (after the fan-on delay time, if any), followed by cold air circulation.

4.Press HEATING SYSTEM to adjust temperature setting above room temperature. The cooling

system should stop operating, the fan should stop running (after the fan-off delay time, if any).

MULTI-STAGE/HEAT PUMP AUXILIARY OPERATION TEST

Follow these steps to energize all stages of hear or cool to permit system checks during installation.

HEAT: Press COOLING SYSTEM to raise temperature setting to 99°F, then hold for five seconds. The second and third stage (heat pump only) heat relays will energize immediately for test purposes. The LED indicator will glow green for first stage and yellow for second stage, and flashing yellow for third stage (heat pump only).

COOL: Press MULTI-STAGE/HEAT PUMP AUXILIARY OPERATION TEST to lower temperature setting to 45°F, then hold for five seconds. The second stage cool relay will energize immediately for test purposes. The LED indicator will glow green for the first stage and yellow for second stage. EMERGENCY (heat pump only): Press SYSTEM to select EMER mode. The LED indicator will glow red for first stage (Aux) in emergency mode.

A flashing red LED indicates a malfunction in the system.

HUMIDIFIER SYSTEM (IF INSTALLED)

1.Press SYSTEM until HEAT is shown at the top of the display.

2.Press the HUMIDITY % button once and

release. Then press theHUMIDIFIER SYSTEM (IF INSTALLED)to the maximum humidity setpoint and hold for 7

seconds until ON is displayed. It assures that the Humidifier will call for humidity when the thermostat calls for HEAT as outlined in the following steps.

3.Press PROGRAM RUN .

4.Press the HOLD button.

5.Press 3.Press PROGRAM RUN . to raise the temperature setting 4°F above room temperature.

The 1st stage (LED Green) and then 2nd stage (LED Yellow) will be energized. The HM terminal will also energize for humidification. The lowercase letter h will appear to the right of HOLD, indicating that the thermostat is calling for Humidification.

6.Press PROGRAM RUN to end the HEAT/HUMIDIFIER test. NOTE: Be sure to press the Humidity button and reset the humidity to the level you desire.

DEHUMIDIFICATION SYSTEM (IF INSTALLED)

1.Press SYSTEM until COOL is shown at the top of the display.

2.Press the HUMIDITY % button once and

release. Then pressDEHUMIDIFICATION SYSTEM (IF INSTALLED) to the minimum humidity setpoint and hold for 7 seconds

until ON is displayed. It assures that the Dehumidifier will call for dehumidifica- tion when the thermostat calls for COOL as outlined in the following steps.

3.Press PROGRAM RUN .

4.Press the HOLD button.

5.Press Manual background to lower the temperature setting 1°F below room temperature. The

1st stage of the cooling system should begin to operate and the LED indicator will glow Green. The lowercase letter d will appear to the right of HOLD, indicating that the thermostat is calling for Dehumidification.

6.Press the temperature Manual background to lower your setpoint 4°F below room temperature, the

DHM terminal will energize causing the FAN to go to high speed.

7.Press the HUMIDITY % button and set your desired dehumidification setpoint

in % RH using the Manual background and Manual background.

8.Press PROGRAM RUN to accept the change.

9