•HOLD TEMPERATURE — The thermostat can hold any temperature within its range for an indefinite period, without reverting to
the program. Press HOLDCOPY . HOLD will be
displayed. Then choose the desired hold
temperature by pressing or . The thermostat will hold the room temperature
at the selected setting until you press PRGMRUN
to start program operation again. This fea- ture is ideal for energy conservation when the building is unoccupied for an extended period of time.
• °F/°C CONVERTIBILITY — Press TIME
FWD
and TIME at the same time until the tem-
BACK
perature display is in °C (Celsius). To dis- play °F, repeat the process.
•ADJUSTABLE HEATING AND COOLING CYCLE TIMES (ANTICIPATION) — If the heating/cooling system is turning on and off too often (short cycles) or not often enough (long cycles), you may want to adjust the anticipation setting.
!CAUTION
A cooling anticipation setting of less than 10 may cause decreased compressor life.
To adjust heat anticipation, press CLOCKSET and
ADV at the same time. The display will
DAY
show HEAT 5 (this is the factory prepro- grammed heating anticipation setting). You may select any heat anticipation setting from 2 to 40 (note that for hydronic sys- tems, a minimum anticipation setting of 15 is recommended).
13