White Rodgers 21D83M-843 Specifications, ELECTRICAL RATINGS @ 77F 25C, Humidity Range, Mounting

Models: 21D83M-843

1 8
Download 8 pages 5.77 Kb
Page 2
Image 2
SPECIFICATIONS

SPECIFICATIONS

ELECTRICAL RATINGS [@ 77°F (25°C)]:

OPERATING TEMPERATURE RANGE:

Input Voltage: 25 VAC 50/60 Hz

-40° to 175°F (-40° to 80°C)

 

 

Max. Input Current @ 25 VAC: 0.45 amp

HUMIDITY RANGE:

 

 

 

Relay Load Ratings:

 

5% to 93% relative humidity (non-condensing)

 

Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf

MOUNTING:

 

 

 

Ignitor Relay: 2.0 amp @ 120 VAC 50/60 Hz

Surface mount multipoise

 

 

 

(resistive)

Timing Specs: (@ 60 Hz**)

 

 

 

Inducer Relay: 2.2 FLA–3.5 LRA @ 120 VAC

 

maximum

 

Circulator Relay: 14.5 FLA–25.0 LRA @ 120 VAC

Flame Establishing Time:

0.8 sec

Flame Current Requirements:

Flame Failure Response Time:

2.0 sec

 

Minimum current to insure flame detection:0.25 µa DC*

**At 50 Hz, all timing specifications should be increased

 

Maximum current for non-detection: 0.1 µa DC*

by 20%

 

 

 

 

 

 

 

Maximum allowable leakage resistance: 100 M ohms

Gases Approved:Natural, Manufactured, Mixed, Liquified

 

Petroleum, and LP Gas Air Mixtures are all approved for use.

*Measured with a DC microammeter in the flame probe lead

 

 

 

 

 

TIMING SPECIFICATIONS

 

 

 

 

(All times are in seconds, unless noted otherwise

 

 

 

 

 

 

 

 

 

Event

 

Definition

50A66-843

 

 

 

 

 

 

 

Pre-Purge

The period of time intended to allow for the dissipation of any unburned

15

 

 

 

gas or residual products of combustion at the beginning of a furnace

 

 

 

 

operating cycle prior to initiating ignition

 

 

 

 

 

 

 

 

Trial for Ignition

The period of time between initiation of gas flow and the action to

4

 

 

Period (TFI)

shut off the gas flow in the event of failure to establish proof of the

 

 

 

 

supervised ignition source or the supervised main burner flame.

 

 

 

Ignition Activation

The period of time between energizing the main gas valve and

4

 

 

Period (IAP)

deactivation of the ignition means prior to the end of TFI

 

 

 

Retries

The additional attempts within the same thermostat cycle for ignition

4 times

 

 

 

when the supervised main burner flame is not proven within the first

 

 

 

 

trial for ignition period.

 

 

 

 

Valve Sequence

Valve sequence period equals 4 seconds trial for ignition period x

20

 

 

Period

(1 initial try + 2 retries) + 12 seconds.

 

 

 

Interpurge

The period of time intended to allow for the dissipation of any unburned

15

 

 

 

gas or residual products of combustion between the failed trial for

 

 

 

 

ignition and the retry period.

 

 

 

 

Post-Purge

The period of time intended to allow for the dissipation of any unburned

5

 

 

 

gas or residual products of combustion at the end of a furnace burner

 

 

 

 

operating cycle. Post-purge begins at the loss of flame sense.

 

 

 

Lockout Time

ANSI standard rated module timing.

250

 

 

 

 

 

 

 

Heat Delay-To-Fan-On

The period of time between proof of the supervised main burner flame

45

 

 

 

and the activation of the blower motor at Heat speed.

 

 

 

Heat Delay-To-Fan-Off*

The period of time between the loss of a call for heat and the

60/90/120/180

 

 

 

deactivation of the blower motor at Heat speed.

 

 

 

Cool Delay-To-Fan-On

The period of time after a thermostat demand for cool before energizing

2

 

 

 

the circulator blower motor at Cool speed.

 

 

 

Cool Delay-To-Fan-Off*

The period of time between the loss of a call for cool and the

2/45

 

 

 

deactivation of the blower motor at Cool speed.

 

 

 

Ignitor Warm-up

The length of time allowed for the igniter to heat up prior to the initiation

20

 

 

 

of gas flow.

 

 

 

 

Auto Reset

After one (1) hour of internal or external lockout, the control will auto-

60 minutes

 

 

 

matically reset itself and go into an auto restart purge for 60 seconds.

 

 

 

Humidifier

 

 

Yes

 

 

 

 

 

 

 

 

Electronic Air Cleaner

 

 

Yes

 

 

 

 

 

 

 

*This time will vary depending on option switch position. The control is factory set at 90 seconds HEAT delay-to-fan-off and 45 seconds COOL delay-to-fan-off. See OPERATION section for further information

2

Page 2
Image 2
White Rodgers 21D83M-843 Specifications, ELECTRICAL RATINGS @ 77F 25C, Operating Temperature Range, Humidity Range, Event