| TROUBLESHOOTING |
|
|
|
| |
|
| DIAGNOSTIC TABLE | ||
|
|
|
|
|
DS 1 (Red) | DS 2 (Green) | Error/Condition | Comments/Troubleshooting | |
Simultaneous | Simultaneous slow | Normal operation | No fault | |
slow flash | flash |
|
|
|
|
|
|
|
|
Simultaneous | Simultaneous | Normal operation with call | Normal operation | |
fast flash | fast flash | for heat |
|
|
|
|
|
|
|
Slow flash | On | Open limit switch | Verify continuity through rollout switch circuit | |
|
|
|
|
|
Off | Slow flash | Pressure switch stuck | Pressure switch stuck closed. Check switch func- | |
|
| closed/open | tion, verify inducer is turning off. | |
|
|
| Pressure switch stuck open. Check pressure switch | |
|
|
| function and tubing. Verify inducer is turning on and | |
|
|
| pulling sufficient vacuum to engage switch. | |
|
|
|
|
|
Alternate | Alternate slow flash | External lockout (retries) | Failure to sense flame is often caused by carbon | |
slow flash |
|
| deposits on the flame sensor, a disconnected or | |
|
|
| shorted flame sensor lead or a poorly grounded | |
|
|
| furnace. Carbon deposits can be cleaned with em- | |
|
|
| ery cloth. Verify sensor is not contacting the burner | |
|
|
| and is located in a good position to sense flame. | |
|
|
| Check sensor lead for shorting and verify furnace | |
|
|
| is grounded properly. | |
|
|
|
|
|
Slow flash | Off | Flame sensed with gas | Verify the gas is operating and shutting down prop- | |
|
| valve | erly. Flame in burner assembly should extinguish | |
|
|
| promptly at the end of the cycle. Check orifices and | |
|
|
| gas pressure. | |
|
|
|
|
|
On | Slow flash | Open rollout switch | Verify continuity through rollout switch circuit. | |
|
|
|
|
|
On | On | Module – internal fault | Module contacts for gas valve not operating or | |
|
| condition | processor fault. Reset control, if condition persists, | |
|
|
| replace module. | |
|
|
|
|
|
Slow flash | Fast flash | Low flame sense current | Low flame sense current is often caused by carbon | |
|
|
| deposits on the flame sensor, a poorly grounded | |
|
|
| furnace or a | |
|
|
| Carbon deposits can be cleaned with emery cloth. | |
|
|
| Check or improve furnace and module ground. | |
|
|
| Verify sensor is located in or very near flame as | |
|
|
| specified by the appliance manufacturer. | |
|
|
|
|
|
Fast flash | Slow flash | Grounding or reversed | Verify the control and furnace are properly ground- | |
|
| polarity | ed. Check and reverse polarity (primary) if incorrect. | |
|
|
|
|
|
Alternate fast | Alternate fast flash | Module ignitor contact | Fault code indicates the module ignitor contacts | |
flash |
| failure | are not functioning properly. Replace module. | |
|
|
|
|
|
7