OPERATION
If flame is detected, then lost, the
If flame is established for more than 10 seconds after igni- tion, the
A momentary loss of gas supply, flame blowout, or a shorted or open condition in the flame probe circuit will be sensed within 2 seconds. The gas valve will
If the control has gone into system lockout, it may be pos- sible to reset the control by a momentary power interrup- tion of ten seconds or longer.Refer to PRECAUTIONARY,
SYSTEM LOCKOUT, AND DIAGNOSTIC FEATURES.
COOL MODE
In a typical system, a call for cool is initiated by closing the thermostat contacts. This energizes the
MANUAL FAN ON MODE
If the thermostat fan switch is moved to the ON position, the circulator fan (heat speed) and optional electronic air cleaner are energized. When the fan switch is returned to the AUTO position, the circulator fan and electronic air cleaner (optional) are
SYSTEM LOCKOUT AND DIAGNOSTIC FEATURES
SYSTEM LOCKOUT FEATURES
When system lockout occurs, the gas valve is
To reset the control after system lockout, do one of the following:
1.Interrupt the call for heat at the thermostat for at least onesecond,butlessthan20seconds(ifflameissensed with the gas valve
2.Interrupt the 24 VAC power at the control for at least ten seconds. You may also need to reset the flame rollout sensor switch.
3.After one hour in lockout, the control will automatically reset itself.
DIAGNOSTIC FEATURES
The