![REPLACING 100925-01, 100925-02,](/images/new-backgrounds/49517/495179x1.webp)
TABLE 2
Type | Existing | Replacement | |
| Control Board | Control Board | |
|
|
| |
| ACB COOL | COOL | |
| ACB HEAT | HEAT | |
| PARK M1 | PARK | |
L1 | PARK M2 | PARK | |
ACC | EAC | ||
120 VAC | |||
120 VAC HOT | LINE | ||
| |||
| 120 VAC TX | XFMR | |
| HTG ACC | HUM | |
| ACB LOW | FAN | |
Neutral | Neutral 120 VAC | Neutral | |
120 VAC | Return (5) | 120 VAC (5) | |
Flame Sense | E33 | FS |
INSTALLATION
PROCEDURE 3
REPLACING 100925-01, 100925-02,
1.Disconnect all electric power and shut off gas supply to the furnace.
2.Remove the access panel
3.Disconnect wiring and remove existing ignition control board.
4.Insert the replacement board into existing holes.
5.Reconnect wiring.
6.Replace access panel.
7.Restore the electrical power and gas supply. Refer to the furnace installation instructions for
OPTION SWITCHES
The option switches on the
OPTION SWITCH POSITIONS
HEAT delay- | Set switch | |
#1 | #2 | |
60 sec. | Off | Off |
90 sec.* | Off | On |
120 sec. | On | Off |
180 sec. | On | On |
COOL delay- | Set switch |
#3 | |
2 sec. | Off |
45 sec.* | On |
|
|
*Factory Setting
HEAT MODE
In a typical system, a call for heat is initiated by closing the thermostat contacts. This starts the
This controller has an adaptive algorithm that reduces ignitor temperature to slightly greater than the minimum temperature required to ignite gas in each particular application. The control measures the line voltage and determines an initial ignitor temperature setting based on the measurement. After each successful ignition, the control lowers the ignitor temperature slightly for the next ignition attempt.The control continues to lower the ignitor temperature until ignition does not occur, and the control
OPERATION
goes into retry mode. For the second attempt to ignite gas within the same call for heat, the control increases the ignitor temperature to the value it was on the third previous successful ignition. After ignition is successful, the control sets the ignition temperature at this value for the next 255 calls for heat, after which the control repeats the adaptive algorithm. The control is constantly making adjustments to the ignitor temperature to compensate for changes in the line voltage.
The 80 VAC Silicon Nitride ignitor manufactured by
At the end of the ignitor
If flame is detected, the
If flame is not detected, both valves are
system lockout. | 5 |
|