36H SERIES

Universal Replacement Electronic Ignition Gas Valve

INSTALLATION INSTRUCTIONS

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

DESCRIPTION

The 36H series gas valve has redundant and main solenoid valves that control gas flow to the main burners, a pressure regulator to maintain a constant outlet pressure, and a two position on/off switch for electrical shutoff. The valves are shipped from the fac- tory set for natural gas non-piloted applications.

See instructions in this document for modifications required if the valve is to be installed on an LP gas and/or piloted gas application.

Model

No. of

Open

 

 

Proven/

HSI

DSI

 

 

 

 

 

 

 

No.

Stages

Characteristics

Intermittent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pilot

 

 

 

 

 

 

 

 

 

 

 

36H32

1

Fast

 

 

Yes

 

 

Yes

Yes

 

 

 

 

 

 

 

36H33

1

Slow

 

 

Yes

 

 

Yes

Yes

 

 

 

 

 

 

 

36H64

2

Fast

 

 

Yes

 

 

Yes

Yes

 

 

 

 

 

 

 

36H65

2

Slow

 

 

Yes

 

 

Yes

Yes

 

 

 

 

SPECIFICATIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure Regulator Adjustment Range ( in W.C.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single

 

 

 

 

 

 

Two Stage

 

 

 

 

 

 

 

 

 

Low

 

 

High

 

Min Diff.

 

 

 

 

Stage

 

 

 

 

 

 

Low to High

Natural Gas

 

2.5 - 5.0

 

1.0 - 3.5

 

2.5 - 5.0

 

1.5

 

LP Gas

 

 

5.0 - 12.0

 

4.0 - 9.5

 

8.0 - 12.0

 

2.5

 

 

 

 

 

 

PIPE SIZES/CAPACITIES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (BTU/hr) at 1” W.C.

 

 

 

 

 

 

 

 

 

 

pressure drop across valve

 

Pipe Sizes

 

 

 

AGA Std. Nat. Gas

 

 

 

LP. Gas

 

Available (inches)

 

 

 

(1,000 btu/ cu. ft.)

 

 

(2,500 btu/cu. ft.)

 

3/4” x 3/4” NPT

 

 

 

300,000

 

 

 

 

 

486,000

 

1/2” x 3/4” NPT

 

 

 

260,000

 

 

 

 

 

421,000

Type of Gas:

Natural Gas

Ambient Temperature: ....

-40° to 175°F

Pressure Rating:

14” W.C. (1⁄2 PSI) max.

Voltage:

24 VAC

Frequency:

50/60 Hz

Current:

Single Stage - .410A

 

Two-Stage - .540A

CONTENTS

 

Description

1

Specifications

1

Precautions

3

Installation

4

System Wiring

 

Adjustment

7

Pressure Regulator Adjustment

 

Lighting Instructions

8

Contents French

9

Contents Spanish

17

www.white-rodgers.com

PART NO. 37-7336A

 

www.emersonclimate.com

1219

Page 1