4.Try a different TV. Different models of TV sets vary greatly in their susceptibility to interference.
Troubleshooting Reference
Table 3-1 Troubleshooting Reference
Problem | Possible Cause | Solution |
|
|
|
AC Product will not operate, | Product rated more than | Use an AC product with a power rating |
red FAULT light is on. | 1350 W, safety overload | less than 1350 W. |
| circuit has tripped. |
|
|
|
|
| Product rated less than | AC product may exceed XPower |
| 1350 W, high starting surge | 1500’s surge capability. Use an AC |
| has tripped overload. | product with starting surge power |
|
| within the unit’s surge rating. |
|
|
|
| Battery pack is discharged | Turn off all AC and DC products and |
| (alarm is sounding). | recharge battery pack. |
|
|
|
| XPower 1500 has overheated | Turn AC Outlets Switch OFF and |
| due to poor ventilation. | allow unit to cool for 15 minutes. |
|
| Remove objects covering ventilation |
|
| areas, then restart. |
|
|
|
Run time is less than | XPower 1500 battery pack is | Recharge using AC charger until |
expected. | not fully charged. | Recharge Indicator is green. |
|
|
|
| AC product power | Check AC product power or “wattage” |
| consumption is higher than | rating (or current draw for DC |
| expected. | accessories) and compare with tables |
|
| in “Battery Operating Times” on |
|
| page |
|
|
|
Measured voltage at AC | Use of standard “average” | |
Outlets is too low. | reading AC voltmeter to read | XPower 1500 requires “true RMS” |
| output voltage. | reading meter, such as Fluke 87 series |
|
| multimeter, for accurate measurement. |
|
|
|
| Battery pack is almost | Check Battery Level Indicator and |
| “empty”. | recharge battery pack as needed. |
|
|
|
Charging light is OFF when | No AC power at wall outlet. | Ensure power is available at wall |
AC Charger is connected. |
| outlet. |
|
|
|