Troubleshooting Reference

 

 

 

 

 

 

Table 4-1

Troubleshooting Reference

 

 

 

 

 

 

 

 

Error/Warning

 

 

 

#

Code on Display

Problem

Possible Cause

Solution

 

 

 

 

 

 

E03: Flashing

Inverter is in back-

The AC output is being

Check that no other source of

 

Fault LED:

EMF (backfeed)

supplied with back-EMF

electrical power is connected

 

Flashing

 

protection

(backfeed).

to the AC output circuits of

 

Alarm: Beeping

shutdown.

 

the inverter. If motor loads are

 

 

 

 

 

on the inverter, it is possible

 

 

 

 

 

that a motor shutdown caused

 

 

 

 

 

back-EMF (backfeed). If the

 

 

 

 

 

problem persists, the motor

 

 

 

 

 

may not be able to be operated

 

 

 

 

 

by this inverter.

 

 

 

 

 

4

E04: Flashing

Inverter is in

E07 warning code is

See solution under error # 7 in

 

Fault LED:

internal over

ignored. (See possible

this table.

 

Flashing

 

temperature

causes under error # 8 in

 

 

Alarm: Beeping

shutdown.

this table).

 

 

 

 

 

 

5

E05: Flashing

Inverter's Input

Poor battery condition

Charge the battery.

 

Fault LED:

Under Voltage

 

Install a new battery.

 

Flashing

 

Warning Alarm is

 

Use proper cable size and

 

Alarm: Beeping

on.

Poor DC wiring

 

 

 

 

 

lengths and make solid

 

 

 

 

 

connections.

 

 

 

 

 

For more information, refer to

 

 

 

 

 

“Selecting Cable Sizes”

 

 

 

 

 

starting on page 2-6 of the

 

 

 

 

 

Installation Guide.

 

 

 

 

 

6

E06: Flashing

Inverter's output

Load applied is above

Reduce the load if continuous

 

Fault LED:

overload warning

the continuous operation

operation is required.

 

Flashing

 

alarm is on.

limit.

 

 

Alarm: Beeping

 

 

 

 

 

 

 

 

7

E07: Flashing

Internal over

Inverter ventilation

Improve ventilation.

 

Fault LED:

temperature

openings are obstructed.

Make sure the inverter’s

 

Flashing

 

warning alarm is

 

ventilation openings are not

 

Alarm: Beeping

on.

 

obstructed.

 

 

 

 

Ambient temperature is

Reduce the ambient

 

 

 

 

too high.

temperature.

 

 

 

 

Load applied is above

Reduce the load if continuous

 

 

 

 

the continuous operation

operation is required.

 

 

 

 

limit.

 

 

 

 

 

 

 

975-0376-01-01

4–3

Page 27
Image 27
Xantrex Technology 5000 manual 975-0376-01-01