COMMON QUESTIONS

Why is the display blank except for the mode lights?

If buttons are not pressed within five seconds, the Remote Panel goes into a sleep mode to conserve energy.

Why is action not immediate?

The Remote Panel waits 15 seconds to determine if any more changes are to be made. At the end of this period, the display goes to sleep and actions previously entered take effect.

When the On/OFF is moved to OFF position, the generator does not stop immediately.

The action from the buttons on the Remote Panel is delayed to ensure that action is required.

How long is the delay from request for thermostat request to generator start?

The time delay is 60 seconds.

What is the low battery set point and how long does the battery voltage have to stay there to initiate a generator start? The Low Battery set point is around 11.5 VDC. The battery voltage must stay at or below 11.5 volts for approximately 15 seconds before the AGS will start the generator.

PARAMETER VALUES

Low battery voltage set point

11.5 VDC

Run time for generator

2 hours

Maximum generator run time

4 hours

Number of generator start tries

3 times

12