TROUBLESHOOTING GUIDE

The following is a list of troubleshooting items. Please see page #8 for the installation diagram. A qualified service technician should be contacted to service your system. Refer to the installation diagram for more information.

PROBLEM

SOLUTION

No lights on the AGS

Check data cable connected to

Remote are on

AGS Remote Panel and AGS

 

Control Module. Check for 12 VDC

 

at AGS Controller (wires #5 and

 

#13).

Generator automatically comes on but does not stay on.

Generator turns on when batteries are charged and air conditioner/heaters are off.

Verify that the Generator Hour Meter Signal (wire #3) is connected to the AGS Control Module.

Verify Battery Sense Positive (wire #12) connection.

Generator does not automatically turn on when AGS control attempts to turn on.

Generator does not automatically turn OFF after the AGS system runs the generator for two hours.

AGS System starts generator at too high of a DC voltage.

Check the preheat, if required (wires #8 and #16) and start signal connections (wires #1 and #9).

If the battery voltage did not rise above 13.5 VDC, this is normal operations. Otherwise check the stop signal connections (wire #2 and #10).

Verify quality of Power/Sense negative connection (wire #13).

13