PRE-INSTALLATION CHECKS
1. FLUE
Model
CL Milner Brick - STMB
|
| With or without flue liner system | mm |
| 150min / 230max |
|
| Round (diameter) | inch |
| 6min / 9max |
Flue/Chimney size |
|
|
| ||
| Without flue liner system Square | mm |
| 230 x 230 | |
|
|
| |||
|
|
|
|
| |
|
| inch |
| 9 x 9 | |
|
|
|
| ||
|
|
|
|
|
|
Flue/Chimney |
|
| m |
| 4.5 |
(minimum height) |
| All products |
|
|
|
| feet |
| 13 | ||
|
|
|
| ||
| Do not connect to systems containing large voids or flues over 230mm (9") square |
|
2. VENTILATION
2.1This appliance requires a constant supply of air to maintain proper combustion and effective flue performance.
2.2An inadequate air supply can result in poor combustion and smoke entering the room which is potentially dangerous.
2.3This supply of air can come from either:
2.4The amount of air required must comply with local building regulations and the rules in force.
2.5If spillage is detected during commissioning then there may be insufficient natural ventilation and an additional air supply will be necessary.
2.6Many older buildings are sufficiently ventilated by natural leakage of air to provide suitable air supply for an appliance of 5kW output or less.
Modern building techniques have reduced the amount of air that leaks in or out of a house. A modern construction with an air tightness of less than 5m3 per hour per m2 requires an air vent for ALL solid fuel appliances including those with a rated heat output of less than 5kW.
NOTE: The air leakage of a modern house is tested at the completion of construction and a certificate issued confirming this.
2.7Ventilation requirements in the UK are as shown in the table below:
A) Traditionally Built Homes
•Where the leakage is greater than 5m3/hour/m2.
•Ventilation normally required = 550mm2 per kW output over 5kW
Output (kw) |
| 4 | 5 | 6 | 7 | 8 | 9 | 10 | |
|
|
|
|
|
|
|
|
|
|
|
| mm2 | None | None | 550 | 1100 | 1650 | 2200 | 2750 |
A | Additional | cm2 | None | None | 5.50 | 11.0 | 16.5 | 22.0 | 27.5 |
ventilation |
|
|
|
|
|
|
|
| |
|
| in2 | None | None | 0.89 | 1.77 | 2.66 | 3.55 | 4.40 |
B) Modern Construction Homes
•Where the leakage is less than 5m3/hour/m2.
•Ventilation normally required = 550mm2 per kW
Output (kw) |
| 4 | 5 | 6 | 7 | 8 | 9 | 10 | |
|
|
|
|
|
|
|
|
|
|
|
| mm2 | 2200 | 2750 | 3300 | 3850 | 4400 | 4950 | 5500 |
B | Additional |
|
|
|
|
|
|
|
|
cm2 | 22.0 | 27.5 | 33.0 | 38.5 | 44.0 | 49.5 | 55.0 | ||
ventilation |
|
|
|
|
|
|
|
| |
|
| in2 | 3.55 | 4.40 | 5.32 | 6.21 | 7.10 | 7.99 | 8.87 |
2.8Permanent air vents should be
2.9If vents open into adjoining rooms or spaces there must be an air vent of at least the same size direct to the outside.
2.10Site the vents where cold draught is unlikely to cause discomfort. This can be avoided by placing vents near ceilings or close to the appliance, see diagram.
17