York 060, 090, 036-048 warranty Cooling Performance Data, Air Conditioner Model No

Models: 060 036-048 090

1 16
Download 16 pages 6.12 Kb
Page 11
Image 11
Manual background

279104-YTG-B-0307

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

E1RA060S(25,46

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

 

G2FD060(S,H)24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSER

ID CFM

 

1600

 

 

1800

 

 

2000

 

ENTERING AIR

ID DB (°F)

85

80

75

85

80

75

85

80

75

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

ID WB (°F)

71

67

63

71

67

63

71

67

63

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

63.0

61.1

60.7

62.9

60.9

61.1

62.9

60.6

61.4

65

 

 

 

 

 

 

 

 

 

 

S.C.

39.6

39.7

40.3

41.6

41.5

42.2

43.7

43.3

44.1

 

 

 

 

 

 

 

 

 

 

 

 

KW

3.71

3.66

3.68

3.71

3.66

3.67

3.71

3.67

3.67

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

62.3

59.8

57.9

62.5

60.0

58.5

62.6

60.1

59.0

75

 

 

 

 

 

 

 

 

 

 

S.C.

39.6

39.3

39.1

41.8

41.3

41.1

43.9

43.3

43.1

 

 

 

 

 

 

 

 

 

 

 

 

KW

4.20

4.14

4.12

4.21

4.15

4.13

4.21

4.16

4.13

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

61.7

58.5

55.1

62.0

59.1

55.9

62.3

59.6

56.6

85

 

 

 

 

 

 

 

 

 

 

S.C.

39.6

38.9

38.0

41.9

41.1

40.1

44.2

43.3

42.2

 

 

 

 

 

 

 

 

 

 

 

 

KW

4.70

4.63

4.57

4.71

4.64

4.58

4.72

4.65

4.60

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

61.0

57.2

52.3

61.5

58.2

53.3

62.0

59.1

54.2

95

 

 

 

 

 

 

 

 

 

 

S.C.

39.6

38.5

36.8

42.0

40.9

39.0

44.4

43.3

41.2

 

 

 

 

 

 

 

 

 

 

 

 

KW

5.19

5.11

5.01

5.21

5.13

5.04

5.22

5.14

5.06

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

58.3

53.9

49.1

59.1

54.7

49.9

60.0

55.6

50.7

105

 

 

 

 

 

 

 

 

 

 

S.C.

38.5

37.2

35.4

41.0

39.6

37.6

43.6

41.9

39.8

 

 

 

 

 

 

 

 

 

 

 

 

KW

5.78

5.67

5.55

5.80

5.69

5.57

5.82

5.71

5.60

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

55.5

50.5

45.9

56.8

51.3

46.5

58.0

52.1

47.1

115

 

 

 

 

 

 

 

 

 

 

S.C.

37.4

35.9

34.0

40.1

38.2

36.2

42.7

40.5

38.3

 

 

 

 

 

 

 

 

 

 

 

 

KW

6.36

6.22

6.08

6.39

6.25

6.11

6.41

6.27

6.13

 

 

 

 

 

 

 

 

 

 

 

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.

Air Handler

Coil

T.C.

S.C.

KW

 

 

 

 

 

MA20DN2,4

FC/MC60D3X

1.00

1.00

1.00

 

 

 

 

 

N1AHD2046

G2FD060(S,H)24

1.00

1.00

1.00

 

 

 

 

 

AHP/SHP60D3X

0.98

0.98

1.02

 

 

 

 

 

F2FP060

0.98

0.98

1.02

 

 

 

 

 

G1FA060S21,24

1.00

1.00

1.00

 

 

 

 

 

G1UA060S21,24

1.00

1.00

1.00

 

 

 

 

 

FC/MC/PC/UC60*3X

1.00

1.00

1.00

 

 

 

 

 

Unitary Products Group

11

Page 11
Image 11
York 060, 090, 036-048 warranty Cooling Performance Data, Air Conditioner Model No