York 2000 installation instructions Normal Maintenance

Models: 2000

1 16
Download 16 pages 32.49 Kb
Page 14
Image 14
MAINTENANCE

511.06-N5Y

WARNING: Failure to properly adjust the total system air quan- tity can result in poor system performance.

After readings have been obtained, remove the tubes and seal the drilled holes in the side panels. 5/16" dot plugs (P/N 029-13880) are available through normal parts ordering procedures.

NOTE: DE-ENERGIZE THE COMPRESSORS BEFORE TAKING ANY TEST MEASUREMENTS TO ENSURE A DRY INDOOR COIL.

 

0.5

 

 

 

 

(IWG)

0.4

 

036

048

060

 

 

 

 

 

 

 

 

 

DROP

0.3

 

 

 

 

 

 

 

 

 

PRESSURE

0.2

 

 

 

 

 

 

 

 

 

 

0.1

 

 

 

 

 

0

 

 

 

 

 

1000

1500

2000

2500

3000

NOMINAL CFM

FIG. 10 - PRESSURE DROP ACROSS A DRY INDOOR

COIL VS. SUPPLY AIR CFM

SECURE OWNER’S APPROVAL: When the system is functioning properly, secure the owner’s approval. Show him the location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature settings within the limitations of the system.

MAINTENANCE

NORMAL MAINTENANCE

CAUTION: Prior to any of the following maintenance proce- dures, shut off all power to the unit to prevent personal injury.

FILTERS - Inspect once a month. Replace disposable or clean permanent type as necessary. DO NOT replace permanent type with disposable.

MOTORS - Indoor fan and outdoor fan motors are permanently lubricated and require no maintenance.

OUTDOOR COIL - Dirt should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean coil, be sure power to the unit is shut off prior to cleaning.

NOTE: Exercise care when cleaning the coil so that the coil fins are not damaged.

Do not permit the outdoor air discharge to be ob- structed by overhanging structures of shrubs.