251934-YTG-J-0910

ZJ180 (15 Ton) (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

180.3

17.1

78.5

67.6

49.8

-

-

-

166.8

18.9

68.4

61.1

43.5

-

-

-

3750

 

72

167.2

16.9

111.3

93.5

75.7

57.9

-

-

154.4

18.7

105.1

87.6

70.0

52.4

-

-

 

67

154.0

16.8

144.1

119.5

101.7

83.9

66.1

-

141.9

18.6

141.9

114.0

96.5

78.9

61.3

-

 

 

 

 

62

143.0

16.6

143.0

143.0

124.7

106.9

89.1

71.3

131.7

18.4

131.7

131.7

120.0

100.6

83.0

65.5

 

 

77

186.6

17.0

95.7

75.3

54.8

-

-

-

172.7

18.8

89.1

68.5

48.1

-

-

-

 

 

72

173.0

16.8

124.3

103.8

83.4

62.9

-

-

159.8

18.6

118.0

97.7

77.3

57.0

-

-

4500

 

67

159.5

16.7

152.9

132.4

111.9

91.5

71.0

-

146.9

18.4

146.9

126.9

106.6

86.2

65.9

-

 

 

62

148.0

16.5

148.0

148.0

137.3

116.8

96.4

75.9

136.4

18.3

136.4

136.4

130.6

110.2

89.9

69.6

 

 

57

149.2

16.6

149.2

149.2

132.8

112.4

91.9

71.5

139.1

18.4

139.1

139.1

123.0

102.7

82.3

62.0

 

 

77

193.0

16.8

113.0

83.0

59.8

-

-

-

178.6

18.6

109.8

75.8

52.7

-

-

-

 

 

72

178.9

16.7

137.3

114.2

91.0

67.9

-

-

165.3

18.4

130.9

107.8

84.7

61.6

-

-

5250

 

67

164.9

16.5

161.6

145.3

122.2

99.1

76.0

-

152.0

18.3

152.0

139.8

116.7

93.6

70.5

-

 

 

62

153.1

16.4

153.1

153.1

149.9

126.8

103.7

80.5

141.1

18.1

141.1

141.1

141.1

119.9

96.8

73.7

 

 

57

154.2

16.5

154.2

154.2

145.0

121.9

98.8

75.6

143.8

18.2

143.8

143.8

134.7

111.6

88.5

65.4

 

 

77

199.3

16.7

130.3

90.7

64.9

-

-

-

184.5

18.5

130.5

83.2

57.3

-

-

-

 

 

72

184.8

16.6

150.3

124.5

98.7

72.9

-

-

170.8

18.3

143.7

117.9

92.0

66.2

-

-

6000

 

67

170.3

16.4

170.3

158.3

132.5

106.7

80.9

-

157.0

18.1

157.0

152.6

126.8

100.9

75.1

-

 

 

62

158.1

16.3

158.1

158.1

162.5

136.7

110.9

85.1

145.8

18.0

145.8

145.8

145.8

129.5

103.6

77.8

 

 

57

159.3

16.3

159.3

159.3

157.2

131.4

105.6

79.8

148.6

18.1

148.6

148.6

146.4

120.5

94.7

68.8

 

 

72

186.1

16.6

158.7

131.5

104.3

77.0

-

-

171.7

18.3

152.1

124.8

97.5

70.2

-

-

6600

 

67

171.5

16.4

171.5

165.5

140.0

112.7

85.5

-

157.9

18.1

157.9

157.9

134.2

106.9

79.7

-

 

62

159.2

16.3

159.2

159.2

161.4

134.2

106.9

79.7

146.6

18.0

146.6

146.6

146.6

124.1

96.8

69.5

 

 

 

 

57

160.4

16.4

160.4

160.4

159.4

132.1

104.9

77.7

149.4

18.1

149.4

149.4

148.3

121.1

93.8

66.5

 

 

72

187.3

16.6

167.1

138.5

109.8

81.2

-

-

172.7

18.3

160.4

131.6

102.9

74.2

-

-

7200

 

67

172.6

16.4

172.6

172.6

147.4

118.8

90.1

-

158.8

18.2

158.8

158.8

141.7

113.0

84.2

-

 

62

160.3

16.3

160.3

160.3

160.3

131.6

102.9

74.3

147.4

18.0

147.4

147.4

147.4

118.7

90.0

61.2

 

 

 

 

57

161.5

16.4

161.5

161.5

161.5

132.8

104.2

75.5

150.3

18.1

150.3

150.3

150.3

121.6

92.8

64.1

1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

22

Johnson Controls Unitary Products

Page 22
Image 22