Air Flow

 

 

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

 

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

(CFM)

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

Standard 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HP & Field

 

 

 

 

Standard 5 HP & Drive

 

 

 

 

 

 

 

High Static 7.5 HP & Drive

 

 

 

 

Supplied

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5200

694

1.43

730

1.89

766

2.32

801

2.72

836

3.09

871

3.42

904

3.71

937

3.95

968

4.14

997

4.28

1025

4.35

1051

4.37

5600

713

1.82

749

2.27

785

2.71

820

3.11

856

3.48

890

3.81

923

4.10

956

4.34

987

4.53

1017

4.67

1045

4.74

1071

4.75

6000

734

2.25

770

2.70

806

3.13

841

3.53

877

3.90

911

4.23

944

4.52

977

4.77

1008

4.96

1038

5.09

1066

5.17

1092

5.18

6400

757

2.71

793

3.17

829

3.60

864

4.00

899

4.37

934

4.70

967

4.99

1000

5.23

1031

5.42

1060

5.56

1088

5.64

1114

5.65

6800

781

3.22

817

3.68

853

4.11

888

4.51

923

4.88

958

5.21

991

5.50

1024

5.74

1055

5.94

1085

6.07

1112

6.15

1139

6.16

7200

807

3.78

843

4.23

878

4.66

914

5.07

949

5.44

983

5.77

1017

6.06

1049

6.30

1081

6.49

1110

6.63

1138

6.70

1164

6.71

7600

834

4.38

870

4.83

905

5.26

941

5.67

976

6.04

1010

6.37

1044

6.66

1076

6.90

1108

7.09

1137

7.23

1165

7.30

1191

7.31

8000

862

5.02

898

5.48

934

5.91

969

6.31

1004

6.68

1039

7.01

1072

7.30

1105

7.55

1136

7.74

1166

7.87

1194

7.95

1220

7.96

8400

892

5.71

928

6.17

963

6.60

999

7.00

1034

7.37

1069

7.70

1102

7.99

1134

8.24

1166

8.43

1195

8.56

-

-

-

-

8800

923

6.45

959

6.91

994

7.34

1030

7.74

1065

8.11

1099

8.44

-

-

-

-

-

-

-

-

-

-

-

-

9200

955

7.23

991

7.68

1026

8.11

1062

8.52

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

9600

988

8.05

1024

8.51

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5 HP & Field Supplied Drive

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.838.