![AIR FLOW](/images/new-backgrounds/35123/3512323x1.webp)
AIR FLOW
AIR FLOW DATA - 60 Hz MODELS - 208 VOLT
Models | Blower |
|
| CFM1 @ External Static Pressure - IWC |
|
| ||
Motor Speed |
|
|
|
|
|
|
| |
| 0.10 | 0.20 | 0.30 | 0.40 | 0.50 | 0.60 | 0.70 | |
|
|
| 208 Volt |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| High #5 | 1074 | 1029 | 999 | 954 | 911 | 865 | 812 |
| Med High #4 | 895 | 846 | 802 | 759 | 701 | 630 | 526 |
AHE18B3XH21 | Med #3 | 663 | 610 | 556 | 482 | 334 | 219 | 173 |
| Med Low #2 | 630 | 466 | 346 | 196 | 170 | 67 | 23 |
| Low #1 | 630 | 466 | 346 | 196 | 170 | 67 | 23 |
| High #5 | 1147 | 1107 | 1076 | 1040 | 992 | 942 | 861 |
| Med High #4 | 1009 | 974 | 941 | 903 | 859 | 811 | 762 |
AHE24B3XH21 | Med #3 | 826 | 785 | 744 | 690 | 639 | 566 | 501 |
| Med Low #2 | 654 | 590 | 556 | 479 | 419 | 307 | 251 |
| Low #1 | 580 | 491 | 425 | 317 | 224 | 189 | 73 |
| High #5 | 1147 | 1107 | 1076 | 1040 | 992 | 942 | 861 |
| Med High #4 | 1009 | 974 | 941 | 903 | 859 | 811 | 762 |
AHE30B3XH21 | Med #3 | 826 | 785 | 744 | 690 | 639 | 566 | 501 |
| Med Low #2 | 654 | 590 | 556 | 479 | 419 | 307 | 251 |
| Low #1 | 580 | 491 | 425 | 317 | 224 | 189 | 73 |
| High #5 | 1473 | 1417 | 1361 | 1304 | 1241 | 1171 | 1109 |
| Med High #4 | 1257 | 1204 | 1138 | 1076 | 1000 | 928 | 856 |
AHE36C3XH21 | Med #3 | 1069 | 997 | 912 | 831 | 772 | 697 | 617 |
| Med Low #2 | 994 | 800 | 705 | 621 | 554 | 488 | 432 |
| Low #1 | 904 | 692 | 411 | 329 | 256 | 152 | NA |
| High #5 | 1619 | 1577 | 1531 | 1484 | 1428 | 1372 | 1307 |
| Med High #4 | 1434 | 1391 | 1346 | 1292 | 1235 | 1164 | 1054 |
AHE42D3XH21 | Med #3 | 1243 | 1192 | 1135 | 1073 | 978 | 882 | 778 |
| Med Low #2 | 1141 | 1027 | 952 | 842 | 724 | 572 | 559 |
| Low #1 | 1025 | 851 | 465 | 418 | 253 | 208 | 123 |
| High #5 | 1847 | 1812 | 1775 | 1725 | 1684 | 1645 | 1600 |
| Med High #4 | 1675 | 1640 | 1597 | 1561 | 1522 | 1479 | 1421 |
AHE48D3XH21 | Med #3 | 1436 | 1394 | 1349 | 1301 | 1246 | 1182 | 1095 |
| Med Low #2 | 1250 | 1211 | 1157 | 1100 | 1013 | 924 | 854 |
| Low #1 | 1151 | 1029 | 965 | 857 | 779 | 720 | 639 |
| High #5 | 2083 | 2042 | 2002 | 1959 | 1921 | 1875 | 1829 |
| Med High #4 | 1893 | 1856 | 1815 | 1776 | 1728 | 1688 | 1639 |
AHE60D3XH21 | Med #3 | 1642 | 1609 | 1564 | 1512 | 1467 | 1416 | 1340 |
| Med Low #2 | 1443 | 1401 | 1360 | 1307 | 1242 | 1160 | 1062 |
| Low #1 | 1259 | 1198 | 1140 | 1067 | 972 | 900 | 797 |
1. Dry coil conditions only, tested without filters.
Air handler units are CSA listed to UL 1995/CSA C22.2
Operation not recommended in shaded areas.
12 | Johnson Controls Unitary Products |