York AHE18 THRU 60 warranty Application Factors - Rated Cfm Vs. Actual Cfm, YTG-B-0311

Models: AHE18 THRU 60

1 14
Download 14 pages 1.27 Kb
Page 5
Image 5
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM

680210-YTG-B-0311

APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM

% Of Rated Airflow (CFM)

80%

90%

100%

110%

120%

 

 

 

 

 

 

Capacity Factor

0.96

0.98

1.00

1.02

1.03

 

 

 

 

 

 

PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)

Models

 

AHE18B

AHE24B

AHE30B

AHE36C

AHE42D

AHE48D

AHE60D

Blower - Diameter x Width

10 x 8

10 x 8

10 x 8

11 x 10

11 x 10

11 x 10

11 x 10

Motor

HP

1/3 HP

1/3 HP

1/3 HP

1/2 HP

1/2 HP

3/4 HP

3/4 HP

Nominal RPM

1050

1050

1050

1050

1050

1050

1050

 

 

Voltage

208/230

208/230

208/230

208/230

208/230

208/230

208/230

Amps

Full Load (230)

2.8

2.8

2.8

4.1

4.1

6.0

6.0

Filter1

Type

 

 

DISPOSABLE OR PERMANENT

 

 

Size

16 x 20 x 1

16 x 20 x 1

16 x 20 x 1

20 x 20 x 1

22 x 20 x 1

22 x 20 x 1

22 x 20 x 1

 

Permanent Type Kit

1PF0601BK

1PF0601BK

1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK 1PF0603BK

Shipping / Operating Weight (lbs.)

115/103

120/105

120/105

152/137

168/150

171/153

174/156

1. Field Supplied.

KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT

FOR

208V

230V

220V

OPERATION MULTIPLY

240V

240V

240V

TABULATED KW & MBH BY

.751

.918

.840

ELECTRICAL DATA - COOLING ONLY (60 Hz)

 

Total Motor Amps

Minimum Circuit Ampacity

Max. O.C.P.1

Minimum Wire

Models

 

 

 

 

 

 

 

60 Hertz

 

60 Hertz

 

 

Amps/Type

Size A.W.G.

 

 

 

 

 

 

 

 

208V

 

230V

208V

 

230V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AHE MODELS

 

 

 

 

 

 

 

 

 

 

 

 

 

AHE18B3XH21

2.8

 

2.8

3.5

 

3.5

15

14

AHE24B3XH21

2.8

 

2.8

3.5

 

3.5

15

14

AHE30B3XH21

2.8

 

2.8

3.5

 

3.5

15

14

AHE36C3XH21

4.1

 

4.1

5.1

 

5.1

15

14

AHE42D3XH21

4.1

 

4.1

5.1

 

5.1

15

14

AHE48D3XH21

6.0

 

6.0

7.5

 

7.5

15

14

AHE60D3XH21

6.0

 

6.0

7.5

 

7.5

15

14

1.OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. * May be 0 (no Circuit Breaker) or 1 (with Circuit Breaker).

Johnson Controls Unitary Products

5

Page 5
Image 5
York AHE18 THRU 60 warranty Application Factors - Rated Cfm Vs. Actual Cfm, PHYSICAL & ELECTRICAL DATA - COOLING ONLY 60 Hz