APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow (CFM) | 80% | 90% | 100% | 110% | 120% |
|
|
|
|
|
|
Capacity Factor | 0.96 | 0.98 | 1.00 | 1.02 | 1.03 |
|
|
|
|
|
|
PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models |
| AHE18B | AHE24B | AHE30B | AHE36C | AHE42D | AHE48D | AHE60D | |
Blower - Diameter x Width | 10 x 8 | 10 x 8 | 10 x 8 | 11 x 10 | 11 x 10 | 11 x 10 | 11 x 10 | ||
Motor | HP | 1/3 HP | 1/3 HP | 1/3 HP | 1/2 HP | 1/2 HP | 3/4 HP | 3/4 HP | |
Nominal RPM | 1050 | 1050 | 1050 | 1050 | 1050 | 1050 | 1050 | ||
| |||||||||
| Voltage | 208/230 | 208/230 | 208/230 | 208/230 | 208/230 | 208/230 | 208/230 | |
Amps | Full Load (230) | 2.8 | 2.8 | 2.8 | 4.1 | 4.1 | 6.0 | 6.0 | |
Filter1 | Type |
|
| DISPOSABLE OR PERMANENT |
|
| |||
Size | 16 x 20 x 1 | 16 x 20 x 1 | 16 x 20 x 1 | 20 x 20 x 1 | 22 x 20 x 1 | 22 x 20 x 1 | 22 x 20 x 1 | ||
| Permanent Type Kit | 1PF0601BK | 1PF0601BK | 1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK 1PF0603BK | |||||
Shipping / Operating Weight (lbs.) | 115/103 | 120/105 | 120/105 | 152/137 | 168/150 | 171/153 | 174/156 |
1. Field Supplied.
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
FOR
208V
230V
220V
OPERATION MULTIPLY
240V
240V
240V
TABULATED KW & MBH BY
.751
.918
.840
ELECTRICAL DATA - COOLING ONLY (60 Hz)
| Total Motor Amps | Minimum Circuit Ampacity | Max. O.C.P.1 | Minimum Wire | ||||
Models |
|
|
|
|
|
| ||
| 60 Hertz |
| 60 Hertz | |||||
|
| Amps/Type | Size A.W.G. | |||||
|
|
|
|
|
|
| ||
| 208V |
| 230V | 208V |
| 230V |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| AHE MODELS |
|
|
|
|
|
|
|
|
|
|
|
|
|
AHE18B3XH21 | 2.8 |
| 2.8 | 3.5 |
| 3.5 | 15 | 14 |
AHE24B3XH21 | 2.8 |
| 2.8 | 3.5 |
| 3.5 | 15 | 14 |
AHE30B3XH21 | 2.8 |
| 2.8 | 3.5 |
| 3.5 | 15 | 14 |
AHE36C3XH21 | 4.1 |
| 4.1 | 5.1 |
| 5.1 | 15 | 14 |
AHE42D3XH21 | 4.1 |
| 4.1 | 5.1 |
| 5.1 | 15 | 14 |
AHE48D3XH21 | 6.0 |
| 6.0 | 7.5 |
| 7.5 | 15 | 14 |
AHE60D3XH21 | 6.0 |
| 6.0 | 7.5 |
| 7.5 | 15 | 14 |
1.OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. * May be 0 (no Circuit Breaker) or 1 (with Circuit Breaker).