![AIR FLOW DATA - 60 Hz MODELS - 230 VOLT](/images/new-backgrounds/35123/3512325x1.webp)
AIR FLOW DATA - 60 Hz MODELS - 230 VOLT
Models | Blower |
|
| CFM1 @ External Static Pressure - IWC |
|
| ||
Motor Speed |
|
|
|
|
|
|
| |
| 0.10 | 0.20 | 0.30 | 0.40 | 0.50 | 0.60 | 0.70 | |
|
|
| 230 Volt |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| High #5 | 1075 | 1041 | 1003 | 970 | 930 | 885 | 842 |
| Med High #4 | 895 | 845 | 808 | 767 | 709 | 647 | 561 |
AHE18B3XH21 | Med #3 | 663 | 618 | 557 | 490 | 348 | 267 | 192 |
| Med Low #2 | 629 | 468 | 356 | 197 | 175 | 68 | 23 |
| Low #1 | 629 | 468 | 356 | 197 | 175 | 68 | 23 |
| High #5 | 1156 | 1120 | 1093 | 1056 | 1014 | 951 | 862 |
| Med High #4 | 1021 | 987 | 952 | 918 | 873 | 836 | 787 |
AHE24B3XH21 | Med #3 | 829 | 789 | 754 | 698 | 654 | 585 | 532 |
| Med Low #2 | 681 | 621 | 575 | 496 | 435 | 336 | 262 |
| Low #1 | 598 | 503 | 437 | 340 | 259 | 203 | 74 |
| High #5 | 1156 | 1120 | 1093 | 1056 | 1014 | 951 | 862 |
| Med High #4 | 1021 | 987 | 952 | 918 | 873 | 836 | 787 |
AHE30B3XH21 | Med #3 | 829 | 789 | 754 | 698 | 654 | 585 | 532 |
| Med Low #2 | 681 | 621 | 575 | 496 | 435 | 336 | 262 |
| Low #1 | 598 | 503 | 437 | 340 | 259 | 203 | 74 |
| High #5 | 1465 | 1415 | 1360 | 1307 | 1246 | 1183 | 1118 |
| Med High #4 | 1260 | 1204 | 1142 | 1075 | 1008 | 946 | 876 |
AHE36C3XH21 | Med #3 | 1088 | 1022 | 939 | 862 | 782 | 721 | 626 |
| Med Low #2 | 998 | 810 | 717 | 630 | 562 | 493 | 444 |
| Low #1 | 903 | 707 | 411 | 323 | 265 | 152 | NA |
| High #5 | 1632 | 1589 | 1542 | 1494 | 1446 | 1391 | 1335 |
| Med High #4 | 1430 | 1390 | 1346 | 1294 | 1238 | 1168 | 960 |
AHE42D3XH21 | Med #3 | 1238 | 1198 | 1145 | 1082 | 993 | 908 | 805 |
| Med Low #2 | 1118 | 1020 | 947 | 851 | 734 | 666 | 563 |
| Low #1 | 998 | 772 | 477 | 418 | 349 | NA | NA |
| High #5 | 1861 | 1823 | 1787 | 1750 | 1708 | 1666 | 1620 |
| Med High #4 | 1674 | 1640 | 1599 | 1562 | 1516 | 1472 | 1432 |
AHE48D3XH21 | Med #3 | 1442 | 1405 | 1358 | 1311 | 1262 | 1197 | 1108 |
| Med Low #2 | 1257 | 1220 | 1163 | 1103 | 1031 | 942 | 864 |
| Low #1 | 1153 | 1031 | 967 | 867 | 764 | 718 | 633 |
| High #5 | 2091 | 2053 | 2016 | 1975 | 1937 | 1906 | 1869 |
| Med High #4 | 1903 | 1868 | 1832 | 1791 | 1748 | 1703 | 1660 |
AHE60D3XH21 | Med #3 | 1634 | 1598 | 1562 | 1516 | 1468 | 1422 | 1350 |
| Med Low #2 | 1447 | 1404 | 1361 | 1318 | 1257 | 1164 | 1092 |
| Low #1 | 1268 | 1203 | 1148 | 1073 | 978 | 907 | 839 |
|
|
|
|
|
|
|
|
|
1. Dry coil conditions only, tested without filters.
Air handler units are CSA listed to UL 1995/CSA C22.2
Operation not recommended in shaded areas.
Johnson Controls Unitary Products | 13 |