TYPICAL APPLICATIONS

 

 

 

 

 

 

 

680210-YTG-B-0311

Electrical Data - (For Single Source Power Supply) - Copper Wire - 208/230-3-60

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Kit -

Heater

 

 

Field Wiring

 

 

 

 

 

 

 

 

 

Models

Amps

Min. Circuit Ampacity

Max. O.C.P.1 Amps/Type

75°C Wire Size - AWG

Three Phase

 

240V

 

 

 

 

 

 

 

 

208V

230V

208V

230V

208V

230V

 

 

 

 

 

 

 

 

 

 

 

 

AHE24B3XH21

6HK06501525

34.6

41.0

44.95

45

50

8

8

 

 

 

 

 

 

 

 

 

AHE30B3XH21

6HK06501525

34.6

41.0

44.95

45

50

8

8

 

 

 

 

 

 

 

 

 

AHE36C3XH21

6HK06501525

34.6

42.6

46.57

45

50

8

8

 

 

 

 

 

 

 

 

6HK16502025

46.2

55.2

60.47

60

70

6

4

 

 

 

 

 

 

 

 

 

 

AHE42D3XH21

6HK06501525

34.6

42.6

46.57

45

50

8

8

 

 

 

 

 

 

 

 

6HK16502025

46.2

55.2

60.47

60

70

6

4

 

 

 

 

 

 

 

 

 

 

AHE48D3XH21

6HK06501525

34.6

45.0

48.95

50

50

8

8

 

 

 

 

 

 

 

 

6HK16502025

46.2

57.6

62.84

60

70

6

4

 

 

 

 

 

 

 

 

 

 

 

6HK06501525

34.6

45.0

48.95

50

50

8

8

AHE60D3XH21

 

 

 

 

 

 

 

 

6HK16502025

46.2

57.6

62.84

60

70

6

4

 

 

 

 

 

 

 

 

 

 

6HK16502525

57.7

70.0

76.62

80

80

4

4

 

 

 

 

 

 

 

 

 

1.O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

2.Heaters are 3 Phase.

Electrical Data - (For Multi-Source Power Supply) - Copper Wire - 208/230-3-60

 

 

Minimum Circuit Ampacity

Max. O.C.P.1 Amps/Type

75°C Wire Size - AWG

Models

Heater

 

 

 

Circuit

 

 

Model

 

 

 

 

 

 

 

 

1st

2nd

1st

 

2nd

1st

2nd

 

 

 

 

 

208/230

208/230

208/230

 

208/230

208/230

208/230

AHE36C3XH21

6HK16502025

30.1/34.0

25/28.9

35/35

 

30/30

10/10

10/10

AHE42D3XH21

6HK16502025

30.1/34.0

25/28.9

35/35

 

30/30

10/10

10/10

AHE48D3XH21

6HK16502025

32.5/36.4

25/28.9

35/40

 

30/30

10/8

10/10

AHE60D3XH21

6HK16502025

32.5/36.4

25/28.9

35/40

 

30/30

10/8

10/10

6HK16502525

38.8/43.6

31.3/36.1

40/45

 

35/40

8/8

10/8

 

 

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

TYPICAL APPLICATIONS

UPFLOW

HEAT

HEAT

HORIZONTAL RIGHT

HEAT

HORIZONTAL LEFT

ACCESSORIES

Refer to Price Manual for specific model numbers where not shown.

TXV Kits - TXV kits are available for “Flex-coil” applications and converting R-22 to R-410A or as a service replacement. All kits are bolt-on and require no brazing to install.

Electric Heaters - 6HK models shown under electrical data include sequential operation and temperature dual limit switches for safe, efficient operation. Circuit breakers are pro- vided where shown.

LIMITATIONS

These units must be wired and installed in accordance with all national and local safety codes.

Voltage limits are as follows:

Air Handler Voltage

Voltage code

1Normal Operating

Voltage Range

 

 

 

 

 

208/230-1-60

06

187-253

 

 

 

1. Rated in accordance with ARI Standard 110, utilization range “A”.

Airflow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units.

 

Entering Air Temperature Limits

 

Wet Bulb Temp.°F

Dry Bulb Temp. °F

Min.

Max.

Min.

Max.

57

72

65

95

Johnson Controls Unitary Products