York B3CH 048 and 060 Lockout Control, Checking Supply Airflow, Belt Adjustment, 1743518

Models: B3CH 048 and 060

1 16
Download 16 pages 54.58 Kb
Page 13
Image 13
LOCKOUT CONTROL

During troubleshooting, the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module. The pegs are 13mm (CHECKING SUPPLY AIRFLOW12in.) long, 1mm (3FIG. 9 - BELT ADJUSTMENT16in.) apart and are mounted on a white base. See Figure 8.

LOCKOUT CONTROL

Any one of four conditions will put the system into a lock-out condition during the heating or cooling mode:

1.The discharge line temperature reaches 124°C (255°F) (102°C [215°F] reset) or,

2.The discharge pressure reaches 2770 kPa (398 PSIG) (2158 kPa [310 PSIG] reset) or,

3.The suction line freezestat equals -3°C (26°F) (3°C [38°F] reset) or,

4.The low-pressure cut-out equals 49 kPa (7 PSIG) (153 kPa [22 PSIG] reset).

A lock-outl energizes the emergency heat light on the thermostat and the red LED light on the unit relay board. Turning the thermostat switch to “Off” then back to “On”, will reset the system.

NOTICE TO OWNER:

If a lockout occurs, check for the following problems before calling a serviceman:

1.Dirty filters.

2.Snow accumulation.

3.Leaf or debris blockage.

After eliminating the problem, attempt to restart the system as follows:

turn the system switch on the thermostat to its “OFF” position for 10 seconds.

turn it back to its original position.

If the unit doesn't start, call a serviceman.

NOTE: Models with an anti-recycle accessory will have a 5- minute delay before starting.

CHECKING SUPPLY AIRFLOW

The speed of the supply air blower will depend on the required airflow, the unit accessories and the static resistances of both the supply and the return air duct systems. With this information, the speed for the supply air blower can be

TABLE 10 - BELT-DRIVE SUPPLY AIR MOTOR PULLEY ADJUSTMENT

TURNS

BLOWER DRIVE RANGE (RPM)

OPEN*

060

5

850

4

916

3

982

2

1048

1

1114

0

1180

*Pulley can be adjusted in half-turn increments.

determined from the blower performance and static resistance data on Tables 4, 5 and 7.

Knowing the required blower RPM and the blower motor kW (HP), the speed setting for the supply air motor can be determined.

The setting (turns open) for the optional belt-drive supply air pulley can be determined from Table 10.

OPTIONAL BELT-DRIVE BLOWER

All units with belt-drive blowers have single speed motors. The variable pitch pulley on the blower motor can be adjusted to

035-12984-001-A-0204

FIG. 9 - BELT ADJUSTMENT

obtain the desired supply airflow. Refer to Table 6 for blower motor drive data. The tension on the belts should be adjusted as shown in Figure 9.

Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other than the equipment installer.

To check the supply airflow after the initial balancing has been completed:

1641912

1743518

5161743518 “ HOLES

DAMPER

 

 

ASSEMBLY

INDOOR

533

 

COIL

21"

FILTERS

 

 

 

DUCT FLANGES

FRONT OF UNIT

 

 

L.H. END VIEW

 

(Back of Unit)

(Filter Access End)

FIG. 10 - HOLE LOCATIONS (PRESS. DROP READING)

1.Drill two 8mm (FIG. 10 - HOLE LOCATIONS (PRESS. DROP READING) in.) holes in the side panels as shown in Figure 10.

2.Insert at least 203mm (8 in.) of 6mm (Manual background in.) tubing into each of these holes for sufficient penetration into the air flow on both sides of the indoor coil.

NOTE: The tubes must be inserted and held in a position per- pendicular to the air flow so that velocity pressure does not affect the static pressure readings.

Unitary Products Group

13

Page 13
Image 13
York B3CH 048 and 060 Lockout Control, Checking Supply Airflow, Belt Adjustment, Hole Locations Press. Drop Reading