During troubleshooting, the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module. The pegs are 13mm (12in.) long, 1mm (316in.) apart and are mounted on a white base. See Figure 8.
LOCKOUT CONTROL
Any one of four conditions will put the system into a
1.The discharge line temperature reaches 124°C (255°F) (102°C [215°F] reset) or,
2.The discharge pressure reaches 2770 kPa (398 PSIG) (2158 kPa [310 PSIG] reset) or,
3.The suction line freezestat equals
4.The
A
NOTICE TO OWNER:
If a lockout occurs, check for the following problems before calling a serviceman:
1.Dirty filters.
2.Snow accumulation.
3.Leaf or debris blockage.
After eliminating the problem, attempt to restart the system as follows:
•turn the system switch on the thermostat to its “OFF” position for 10 seconds.
•turn it back to its original position.
If the unit doesn't start, call a serviceman.
NOTE: Models with an
CHECKING SUPPLY AIRFLOW
The speed of the supply air blower will depend on the required airflow, the unit accessories and the static resistances of both the supply and the return air duct systems. With this information, the speed for the supply air blower can be
TABLE 10 -
TURNS | BLOWER DRIVE RANGE (RPM) |
OPEN* | 060 |
5 | 850 |
4 | 916 |
3 | 982 |
2 | 1048 |
1 | 1114 |
0 | 1180 |
*Pulley can be adjusted in
determined from the blower performance and static resistance data on Tables 4, 5 and 7.
Knowing the required blower RPM and the blower motor kW (HP), the speed setting for the supply air motor can be determined.
The setting (turns open) for the optional
OPTIONAL
All units with
FIG. 9 - BELT ADJUSTMENT
obtain the desired supply airflow. Refer to Table 6 for blower motor drive data. The tension on the belts should be adjusted as shown in Figure 9.
Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other than the equipment installer.
To check the supply airflow after the initial balancing has been completed:
1641912 | 1743518 |
“ | “ |
516 “ HOLES
DAMPER |
|
|
ASSEMBLY | INDOOR | 533 |
| COIL | 21" |
FILTERS |
| |
|
| |
DUCT FLANGES | FRONT OF UNIT |
|
| L.H. END VIEW |
|
(Back of Unit)
(Filter Access End)
FIG. 10 - HOLE LOCATIONS (PRESS. DROP READING)
1.Drill two 8mm ( in.) holes in the side panels as shown in Figure 10.
2.Insert at least 203mm (8 in.) of 6mm ( in.) tubing into each of these holes for sufficient penetration into the air flow on both sides of the indoor coil.
NOTE: The tubes must be inserted and held in a position per- pendicular to the air flow so that velocity pressure does not affect the static pressure readings.
Unitary Products Group | 13 |